English
6 / 6
SPS004-SPS100
7 Troubleshooting
Yes
No
No
No
Yes
Yes
No
FAULT
CAUSE
REMEDY
Cooling air outlet too
high / High dew point
Overload protector (SK/
HT) tripped
Compressor noisy
Excessive
current
consumption
High pressure drop on
air side
High refrigerant dis-
charge
pressure
Condenser dirty
Ambient tem-
perature over
122°F (50°C)
Compressor
components
perished
Condenser dirty
Heat exchanger fouled
with debris
Temperature sensor
calibration
error or
damaged
Clean
condenser
Reduce
temperature
Repair or
replace
compressor
Clean
condenser
Replace
sensor
Seek external as-
sistance
Ice formation on evapora-
tor (low evaporation
pressure)
By-pass air fl ow keep-
ing air inlet open. Open
condensate drain valve
manually.
Restart appliance checking
setting of expansion
valve.
Condenser
dirty
Fan does
not work
Replace
fan
Clean
condenser
Clean heat exchanger
(blow compressed air
in opposite direction to
operating air fl ow). Fit/
renew prefi lter
Fan does
not work
Compressor
winding insulation
partially perished
(compressor
too hot)
Repair
fan
Fan does not work
Excessive
thermal load (compressor
head too hot)
Reduce
compressed air
quantity or air
temperature
Repair
fan
Insuffi cient refriger-
ant: repair any leaks and
recharge the circuit
Low current
consumption
Yes
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Summary of Contents for StarlettePlus-E
Page 2: ......
Page 142: ...8 7 REFRIGERANT CIRCUIT 14 SPS004 SPS100...
Page 143: ...8 8 WIRING DIAGRAM 15 SPS004 SPS100...
Page 144: ...8 8 WIRING DIAGRAM 16 SPS004 SPS100 SPS 004 040 SPS 052 062 SPS 080 100...
Page 145: ...8 8 WIRING DIAGRAM 17 SPS004 SPS100...
Page 147: ......