Installation Instructions for 4041-5300 Electrical Connection Kit
for Self-Regulating Bundles
Instructions for Power Connection
Note: These steps should be followed if making a power connection.
1
If using heat shrink boots, place heat
shrink boot onto bundle and feed
heater wire, tube, and other acces-
sories through openings. Heat boot
carefully until it shrinks down and all
ends are completely sealed. (HSB-2
2-leg boot shown is sold separately.
RTV-103BLK sealant supplied with
kit can also be used instead of HSB’s
to seal bundle ends).
Follow steps 1 through 4 of
“Instructions for Splice or Tee
Connections.”
2
3
Once in place, prepare heating
cable end per “Heating Cable
Preparation,” steps 1 through 6.
5
Parker Hannifin Corporation
Parflex Division
Ravenna, OH USA
www.parker.com/pfd
4
Once cable preparation is complete,
twist junction box onto the pipe
standoff.
Make electric splice connection
inside box with heating cable and
cable from power source. Using two
butt splice connectors, splice heater
bus wires to power source
Using ring terminals, crimp terminal
rings onto braided pigtail and tighten
to back of box with ground screw.
Wrap bus wire connections
with fiberglass tape. Bus wire
connections must not touch inside
box, otherwise a short circuit will
occur.
Butt Splice
Connectors
(before FC
tape applied)
Braided
Ground
Wire
FC Tape
Fitting used in connection
can be obtained from your
local Parker Instrumentation
Distributor.
Typical Power Connection
HSB or
RTV-103BLK
sealant