Installation Instructions for 4041-5300 Electrical Connection Kit
for Self-Regulating Bundles
Heating Cable Preparation: Used in all connection types.
Note: These steps should be followed at the point where “Heating Cable Preparation” is noted in
the instructions.
WARNING
Do not cut through the metal braid
of the heating cable. Effective
ground cannot be made if the
metal braid is removed.
1
Score the outer insulation 6.5 inches
from the end of the cable. Lightly cut
the outer jacket up the center to the
end of the heating cable and peal off
the outer jacket.
2
Push braid back toward outer jacket
to create a pucker.
3
At the bulge, separate the braid
to make an opening in the braid
without cutting it.
4
While bending the heating cable,
work the cable through the braid
opening. Pull the braid tight.
5
Score the inner jacket that is under
the braid 3 inches from the end.
Lightly cut the jacket up the center
to the end of heating cable and peal
away that section.
6
Shave the core material from
outside of each bus wire.
6
Parker Hannifin Corporation
Parflex Division
Ravenna, OH USA
www.parker.com/pfd