background image

20

IA VRD UK.INDD RH 02.06

Digital Power Amplifier

Series VRD350 and VRD355

Installation Manual

Parker Hannifin GmbH & Co. KG

Hydraulic Controls Division

2.4. Diagnosis
Test Sockets

The sockets for I

A

 and I

B

 can be used to measure 

the  solenoid  currents  independently. The  volt-
age  at  the  socket  is  roughly  proportional  to  the 
solenoid current. The voltage is around 1V at 1A. 
At the socket S6 for the sum total of both analog 
command signals (SW5 and SW6), the measured 
value  appears  according  to  the  input  signals.  At 
the socket for the actual value (A), the measured 
value is proportional to the actual value signal. The 
measured value is analogous to display U11.

Internal  Diagnostic  Parameters  (U-Parame-
ters)

Internally computed values can be displayed on the 
7-segment display during normal operation and to 
aid  commissioning  and  trouble  shooting. Values 
should be interpreted as voltage or current with a 
resolution standardised in the display at 10mV to 
9.99V. The relevant position in the software func-
tions can be taken from the block diagrams. For 

U1

Command signals

Display

in V

U2

Value after the ramp generator

U3

Value after the linearisation table

U4

Value after amplifier gain adjustment

U5

Signal to solenoid A

U6

Signal to solenoid B

U7

Solenoid A current

Display

in mA or A

U8

Solenoid B current

U9

Total current solenoid A + solenoid B

The  following  values  are  available  in  the  basic 
version:

Further  outputs  are  available  with  the  feedback 
option card:

U10

Command signal, reference input variable

Display

in V

U11

Feedback value controlled variable

U12

Control difference (error)

U13

Controller output (correcting variable)

Note

Parameter  setting  and  diagnostics  only  possible 
for VRD355 using ABG35S.

Only  trained  staff  should  make  pa-
rameter  changes. The  drive  should 
be switched off whilst adjusting para-
meters.

2.5. Parameters

S-Parameters

Command signals and ramp times are adjusted by 
means of S-Parameters. They may be set during 
normal operation and the alteration is immediately 
effective.

Display

S1...S4

  Command signals as voltage

0...9.99V

S5...S8

 

Ramp times in seconds
(increment 0.01s)

0...9.99s

(increment 0.1s)

10...39.5s

S5

Ramp from 0 to - 

(A-Solenoid)

S6

Ramp from - to 0

(A-Solenoid)

S7

Ramp from 0 to +

(B-Solenoid)

S8

Ramp from + to 0

(B-Solenoid)

H-Parameters (auxiliary parameters)

Parameters H1 and H2 are used in the commission-
ing phase or in test and measurement sequences 
for  simple  input  of  command  signals  (command 
signal simulation). This allows a command signal to 
be input independent of external inputs (command 
signal 5/ command signal 6 or selection of S1 to 
S4  and  a  direction),  without  requiring  additional 
external circuitry.

Parameters can be set during operation. Any al-
teration with 

 and 

 is immediately effective. The 

polarity sign shows which of the two output stages 
or solenoids the command signal acts on.

 

Positive sign  

Solenoid B

 

Negative sign  

Solenoid A

All  command  signals  are  also  additive  in  the  H 
mode. This  means  that  when  command  signals 
are input (internally S1 to S4 and externally SW5 to 
SW6), these are added to active H-parameters, tak-
ing into account the signs. By switching over from H 
1 to H2, or the reverse, it is possible to switch over 
to different values - also with opposite sign.

This is only an auxiliary function. Pre-
cise  measured  values,  comparable 
with a multimeter, are not possible for 
technical reasons.

The enable signal must be present so 
that  the  output  stages  are  active  and 
current can flow.

Summary of Contents for VRD355 Series

Page 1: ...ision Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 Fax 49 2131 513 230 E mail infohcd parker com Copyright 2003 Parker Hanni n GmbH Co KG Bulletin HY11 AL287 M1 UK Installation Manual Se...

Page 2: ...lectoruseanyproductorsystem it is important that you analyse all aspects of your application and review the information concerning the product or system in the current product catalogue Due to the var...

Page 3: ...n Generators 24 3 3 Offset 25 3 4 Valve Curve Linearisation 25 3 5 Adjustment of Current Gain 25 3 6 Dither 25 3 7 Current Controller 25 3 8 Output Stages 25 3 9 Step Functions 26 3 10 Control Circuit...

Page 4: ...Simple operation by 4 entry keys and 3 digit LED display Fault indication by numeric code Variable dither amplitude and frequency Gain for solenoids A and B can be set indepen dantly Different valve c...

Page 5: ...0 10 150kOhm Digital 0 V 0 1 1 V 3 30 Outputs Ext supply voltage V 24 10 ripple 5 Reference V 10 10 10mA Analogue V 0 10 5mA Digital mA 50 Solenoids A 0 8 2 7 3 5 Interfaces Serial RS 232C Adjustment...

Page 6: ...enoids or position indicator with 7 5V null voltage Code Ext closed loop 0 without 0 0 10V 1 4 20mA 2 0 20mA Code Sensor assignment 01 controlled 12 Flow valves NG6 22 Directional valves NG6 32 Direct...

Page 7: ...ence The following devices are to be regarded as strong sources of interference Switching power supply units Frequency converters Drive modules Mains lters with wiring even if screened AC DC commutato...

Page 8: ...ke a potential equalisation Use only cables with a Cu screening grid and a covering of 85 whenever possible Avoid screening lms The screen may not be interrupted along the entire length of the cable I...

Page 9: ...Digital Power Ampli er Series VRD350 and VRD355 Installation Manual 9 IA VRD UK INDD RH 02 06 Parker Hanni n GmbH Co KG Hydraulic Controls Division 1 4 Block Diagram Entire System...

Page 10: ...RD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division Feedback Option hardware only with boards for closed loop...

Page 11: ...7 5V Voltage input without terminating resistance Used for potentiometric transmitter systems in which the loop current is limited to smal values Linearity of the transmitter signal is maintained Cur...

Page 12: ...le emergency stop measures must be taken Application Construction and Operation of ABG35S The ABG35S plug in control unit is used in con junction with the VRD355 proportional ampli er It can easily be...

Page 13: ...anni n GmbH Co KG Hydraulic Controls Division 2 2 Programming Programming Instructions for U S P and E Values Select mode U1 S1 P1 or E1 can be selected Select address Display contents e g S2 has the...

Page 14: ...he ampli er This setting depends on the type of ampli er see also type code This basic setting can be recovered from memory by pressing the 4 keys at the same time up to 10 seconds after the supply vo...

Page 15: ...Hydraulic Controls Division 2 3 Block Diagram Open Loop Control Software functions Open loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 16: ...Hydraulic Controls Division Closed Loop only with boards for closed loop systems Closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 17: ...systems External closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals and ramps H parameter auxiliary parameters P parameter operating...

Page 18: ...vision Remote Loop Control only with boards for closed loop systems Remote loop control external closed loop E2 2 Parameter functions U parameter display of internal measured values S parameter intern...

Page 19: ...lic Controls Division Bypass Controller only with boards for closed loop systems Bypass controller Parameter functions U parameter display of internal measured values S parameter internal command sign...

Page 20: ...cting variable Note Parameter setting and diagnostics only possible for VRD355 using ABG35S Only trained staff should make pa rameter changes The drive should be switched off whilst adjusting para met...

Page 21: ...3 03 V of 0 30 a setpoint of 3 V corresponds to 30 see also page 25 section 3 6 P6 Dither frequency variable in steps from 0 to 647 Hz steps 0 16 40 60 80 110 130 160 220 327 647 in Hz See also page...

Page 22: ...trol only with boards for closed loop systems not active 0 active 1 remote loop control 2 bypass control 3 safety function active only with E14 1 4 E3 Solenoid type 3 5A 9V solenoid coil 1 8 1 reserve...

Page 23: ...data in ABG35S S Load data to ampli er L E16 Activates action selected with E15 Proceeding Press button E The display shows the function selec tedpreviously with parameter E15 S or L Activate the data...

Page 24: ...al Command Signal 5 and Command Signal 6 SW5 and SW6 The command signal inputs 5 and 6 are de signed for signals 0 10 V These setpoints are also passed through the ramp function generator ramp if E8 1...

Page 25: ...dither signal reduces the hysteresis of spool movement Generally low frequency signals are more effective however they may result in noticeable disturbances noise oscil lations Values between 80Hz for...

Page 26: ...or selections 1 to 6 U13 can be positive or negative depending on the difference between feedback and set value Then either solenoid A or B is energized 3 11 To set Zero Point General Case Place the f...

Page 27: ...KP P share of the PID controller P15 has no function E14 0 set Parameter P14 can be used to program a T portion delayingtimefunctionelement Effect on P16 The integral portion is determined by P17 whi...

Page 28: ...E g in position control loops the ramps determine the speed of the drive Using the equations given on page 22 enables the computation of parameters from the loop gain factor In cases where these calc...

Page 29: ...pressure sensors we recom mend that great care be taken The zero volt wiring screening and PE connection are critical Faults in the signal can lead to a triggering of the wire break monitor Instabili...

Page 30: ...s preferably used If the actual value now exceeds this comparative value the control switches on Even if the actual value is under the switching threshold the control remains active The signal at the...

Page 31: ...P21 and P22 Setting E2 3 activates the bypass P13 deter mines the gain of the bypass loop P15 is without any function and P16 sets the P portion P17 the I Portion and P18 the D Portion of the PID con...

Page 32: ...s via a so called null mo dem cable The program PROVRD350 355 Order No HR 59 500 010 is available to carry out programming and remote control This permits simple remote control and programming of the...

Page 33: ...e gure page 9 4 3 Malfunction and Error Messages The current in the output stages is monitored in the ampli er If the total current exceeds a speci c limit an electronic cut out responds and switches...

Page 34: ...10V output PE decoupled 10V output 22 Solenoid A Solenoid A Solenoid A 24 Solenoid B Solenoid B Solenoid B 26 Supply 0V Supply 0V Analogue 0 28 Solenoid A Solenoid A Solenoid A 30 Solenoid B Solenoid...

Page 35: ...eshold P15 0 255 P17 I portion 0 255 P18 D portion 0 255 P19 T portion of DT1 element 0 255 P20 Gain for feedback signal 0 00 2 00 P21 Window Set feedback 0 V 0 00 9 99 P22 Window Set feedback 0 V 0 0...

Page 36: ...Setting Basic Version VRD35X 031 00 old new S1 S4 0 S5 S8 0 H1 H2 Set to 0 after commissioning P1 0 00 P2 0 P3 1 00 P4 1 00 P5 0 80 P6 110Hz P7 0 00 P8 0 00 P9 P10 0 00 P11 1 P12 1 P13 0 P14 0 P15 9...

Page 37: ...open loop version Note All screens are to be earthed over a large areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of lett...

Page 38: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical iso...

Page 39: ...real Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isol...

Page 40: ...eal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isola...

Page 41: ...e areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical i...

Page 42: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical is...

Page 43: ...rge areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical...

Page 44: ...44 IA VRD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division...

Reviews: