Digital Power Amplifier
Series VRD350 and VRD355
Installation Manual
23
IA VRD UK.INDD RH 02.06
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Display
E12
Cable fracture detection
(only with boards for closed loop systems)
active
1
not active
0
E13 Serial interface
(see page, section 3.14)
aktiv
1
nicht aktiv
0
E14 Factor for P13 and P16
(nur bei Kartenausf. für Regelkreise)
P13 or P16 * Factor 1
0
P13 or P16 * Factor 1
1
P13 or P16 * Factor 2
2
P13 or P16 * Factor 4
4
P13 or P16 * Factor 8
8
P13 or P16 * Factor 16
16
Select 0 for internal closed loop, values
1 to 16 for external closed loop. E 14 is
automatically zeroed if E2 = 0 or E2 = 3 is
set. On the other hand, E2 = 3 can be set
if E14
≥
1. The factor from E14 then only
affects P16 and not P13. The changeover
in structure by E14 is carried out.
If E14
≥
1 and E2 = 3 the safety function
is not active.
Display
E15
Select load / store for ABG35S
Store data in ABG35S
S...
Load data to amplifier
L...
E16 Activates action selected with E15
Proceeding:
Press button E
The display shows the function selec-
tedpreviously with parameter E15
...S
or
...L
Activate the data transfer:
Press button E (hold pressed) at the same
time press button M twice, the display
flashes. With the arrow button “up” (
⇑
)
the display shows "run". After pressing the
button E, the transfer will start. The display
shows “. . .” for the time of data transfer.
Whilst loading the display shows a “-” for
the time of data storing.
At the amplifier VRD355 with ABG35S the
following error messages may be shown
on the display:
--6 No valid data in the ABG or wrong
software version in the ABG
--7 Read error while reading from
ABG
--8 Write or read error (verify)
Also available with amplifier VRD355:
The data in the ABG have to be com-
patible with the software version in the
amplifier!
Extended parameters E4 to E7 are
mainly for factory settings. E11 and
E12 can only be selected for a limited
range of other transducer types, please
contact the manufacturer. Reserved parameters
must be left at their factory default value.