Digital Power Amplifier

Series VRD350 and VRD355

Installation Manual

Parker Hannifin GmbH & Co. KG

Hydraulic Controls Division

3. Function
3.1. Command signals

In the standard setting with P11 = 1 positive com-
mand  signals  activate  solenoid  B  and  negative 
values solenoid A.

Internal Command Signals (S1 to S4)

•   Four internal set values (S1, S2, S3 and S4) can 

be selected with an associated direction “+” or 
“-”.

•   These inputs are optically isolated and can be 

selected by means of a programmable control-
ler.

•   When  electrical  isolation  is  not  required,  ter-

minal 2d must be bridged by the customer to 
terminal  26bd  and  terminal  32z  to  terminal 
32bd.

•  If both directions are selected at the same time, 

none of the selected command signals will be 
activated.

•   If no direction is selected, no command signal 

will be activated.

•   All four internal command signals are controlled 

by the ramp function generator.

•   Command  signals  are  additive  and  are  inde-

pendent of direction.

•   If several command signals are selected at the 

same time, the total of these command signals 
is subsequently processed.

•   In varying combinations a total of 16 command 

signals can be selected.

External  Command  Signal  5  and  Command 
Signal 6 (SW5 and SW6)

•  The  command  signal  inputs  5  and  6  are  de-

signed for signals 0...±10 V.

•  These setpoints are also passed through the 

ramp function generator (ramp) if E8 = 1. These 
are also added to the other setpoints. If E8 = 0 
they bypass the ramp function generator and 
have a direct and undelayed effect.

•  The  input  for  command  signal  6  is  designed 

as a differential amplifier (within the operating 
voltage range ±15V).

•  The signal for command signals 5 and 6 must 

be standardised to 10V otherwise the A/D con-
verter is overloaded.

Unused  analogue  command  signal 
inputs  should  be  suitably  bridged  to 
analogue OV.

If the sum total of all setpoints exceeds 
9.95V the LED >10V starts to flash.

3.2. Ramp Function Generator S5 to S8

The  command  signals  (S1...S4)  are  integrated 
accordingly  in  the  ramp  function  generator.  The 
ramp time for each change of direction can be set 
independently. Times of 0...39.5 sec. can be set.
The ramp characteristic is assigned as follows:

The ramp function generator can be switched over 
from constant rise rate to constant time base with 
E8. The ramp function generator can be immedi-
ately set to 0 with the reset ramp input (terminal 
18 z) (quick stop).

Folowing example is presented to help clarify:
Example:  E8 = 0 constant time base
 

S1 = 8.00V; S2 = 2.00V; S7 = 6.00s

The  external  command  signals  SW5 
and SW6 bypass the ramp function.

Summary of Contents for VRD355 Series

Page 1: ...ision Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 Fax 49 2131 513 230 E mail infohcd parker com Copyright 2003 Parker Hanni n GmbH Co KG Bulletin HY11 AL287 M1 UK Installation Manual Se...

Page 2: ...lectoruseanyproductorsystem it is important that you analyse all aspects of your application and review the information concerning the product or system in the current product catalogue Due to the var...

Page 3: ...n Generators 24 3 3 Offset 25 3 4 Valve Curve Linearisation 25 3 5 Adjustment of Current Gain 25 3 6 Dither 25 3 7 Current Controller 25 3 8 Output Stages 25 3 9 Step Functions 26 3 10 Control Circuit...

Page 4: ...Simple operation by 4 entry keys and 3 digit LED display Fault indication by numeric code Variable dither amplitude and frequency Gain for solenoids A and B can be set indepen dantly Different valve c...

Page 5: ...0 10 150kOhm Digital 0 V 0 1 1 V 3 30 Outputs Ext supply voltage V 24 10 ripple 5 Reference V 10 10 10mA Analogue V 0 10 5mA Digital mA 50 Solenoids A 0 8 2 7 3 5 Interfaces Serial RS 232C Adjustment...

Page 6: ...enoids or position indicator with 7 5V null voltage Code Ext closed loop 0 without 0 0 10V 1 4 20mA 2 0 20mA Code Sensor assignment 01 controlled 12 Flow valves NG6 22 Directional valves NG6 32 Direct...

Page 7: ...ence The following devices are to be regarded as strong sources of interference Switching power supply units Frequency converters Drive modules Mains lters with wiring even if screened AC DC commutato...

Page 8: ...ke a potential equalisation Use only cables with a Cu screening grid and a covering of 85 whenever possible Avoid screening lms The screen may not be interrupted along the entire length of the cable I...

Page 9: ...Digital Power Ampli er Series VRD350 and VRD355 Installation Manual 9 IA VRD UK INDD RH 02 06 Parker Hanni n GmbH Co KG Hydraulic Controls Division 1 4 Block Diagram Entire System...

Page 10: ...RD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division Feedback Option hardware only with boards for closed loop...

Page 11: ...7 5V Voltage input without terminating resistance Used for potentiometric transmitter systems in which the loop current is limited to smal values Linearity of the transmitter signal is maintained Cur...

Page 12: ...le emergency stop measures must be taken Application Construction and Operation of ABG35S The ABG35S plug in control unit is used in con junction with the VRD355 proportional ampli er It can easily be...

Page 13: ...anni n GmbH Co KG Hydraulic Controls Division 2 2 Programming Programming Instructions for U S P and E Values Select mode U1 S1 P1 or E1 can be selected Select address Display contents e g S2 has the...

Page 14: ...he ampli er This setting depends on the type of ampli er see also type code This basic setting can be recovered from memory by pressing the 4 keys at the same time up to 10 seconds after the supply vo...

Page 15: ...Hydraulic Controls Division 2 3 Block Diagram Open Loop Control Software functions Open loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 16: ...Hydraulic Controls Division Closed Loop only with boards for closed loop systems Closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals an...

Page 17: ...systems External closed loop Parameter functions U parameter display of internal measured values S parameter internal command signals and ramps H parameter auxiliary parameters P parameter operating...

Page 18: ...vision Remote Loop Control only with boards for closed loop systems Remote loop control external closed loop E2 2 Parameter functions U parameter display of internal measured values S parameter intern...

Page 19: ...lic Controls Division Bypass Controller only with boards for closed loop systems Bypass controller Parameter functions U parameter display of internal measured values S parameter internal command sign...

Page 20: ...cting variable Note Parameter setting and diagnostics only possible for VRD355 using ABG35S Only trained staff should make pa rameter changes The drive should be switched off whilst adjusting para met...

Page 21: ...3 03 V of 0 30 a setpoint of 3 V corresponds to 30 see also page 25 section 3 6 P6 Dither frequency variable in steps from 0 to 647 Hz steps 0 16 40 60 80 110 130 160 220 327 647 in Hz See also page...

Page 22: ...trol only with boards for closed loop systems not active 0 active 1 remote loop control 2 bypass control 3 safety function active only with E14 1 4 E3 Solenoid type 3 5A 9V solenoid coil 1 8 1 reserve...

Page 23: ...data in ABG35S S Load data to ampli er L E16 Activates action selected with E15 Proceeding Press button E The display shows the function selec tedpreviously with parameter E15 S or L Activate the data...

Page 24: ...al Command Signal 5 and Command Signal 6 SW5 and SW6 The command signal inputs 5 and 6 are de signed for signals 0 10 V These setpoints are also passed through the ramp function generator ramp if E8 1...

Page 25: ...dither signal reduces the hysteresis of spool movement Generally low frequency signals are more effective however they may result in noticeable disturbances noise oscil lations Values between 80Hz for...

Page 26: ...or selections 1 to 6 U13 can be positive or negative depending on the difference between feedback and set value Then either solenoid A or B is energized 3 11 To set Zero Point General Case Place the f...

Page 27: ...KP P share of the PID controller P15 has no function E14 0 set Parameter P14 can be used to program a T portion delayingtimefunctionelement Effect on P16 The integral portion is determined by P17 whi...

Page 28: ...E g in position control loops the ramps determine the speed of the drive Using the equations given on page 22 enables the computation of parameters from the loop gain factor In cases where these calc...

Page 29: ...pressure sensors we recom mend that great care be taken The zero volt wiring screening and PE connection are critical Faults in the signal can lead to a triggering of the wire break monitor Instabili...

Page 30: ...s preferably used If the actual value now exceeds this comparative value the control switches on Even if the actual value is under the switching threshold the control remains active The signal at the...

Page 31: ...P21 and P22 Setting E2 3 activates the bypass P13 deter mines the gain of the bypass loop P15 is without any function and P16 sets the P portion P17 the I Portion and P18 the D Portion of the PID con...

Page 32: ...s via a so called null mo dem cable The program PROVRD350 355 Order No HR 59 500 010 is available to carry out programming and remote control This permits simple remote control and programming of the...

Page 33: ...e gure page 9 4 3 Malfunction and Error Messages The current in the output stages is monitored in the ampli er If the total current exceeds a speci c limit an electronic cut out responds and switches...

Page 34: ...10V output PE decoupled 10V output 22 Solenoid A Solenoid A Solenoid A 24 Solenoid B Solenoid B Solenoid B 26 Supply 0V Supply 0V Analogue 0 28 Solenoid A Solenoid A Solenoid A 30 Solenoid B Solenoid...

Page 35: ...eshold P15 0 255 P17 I portion 0 255 P18 D portion 0 255 P19 T portion of DT1 element 0 255 P20 Gain for feedback signal 0 00 2 00 P21 Window Set feedback 0 V 0 00 9 99 P22 Window Set feedback 0 V 0 0...

Page 36: ...Setting Basic Version VRD35X 031 00 old new S1 S4 0 S5 S8 0 H1 H2 Set to 0 after commissioning P1 0 00 P2 0 P3 1 00 P4 1 00 P5 0 80 P6 110Hz P7 0 00 P8 0 00 P9 P10 0 00 P11 1 P12 1 P13 0 P14 0 P15 9...

Page 37: ...open loop version Note All screens are to be earthed over a large areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of lett...

Page 38: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical iso...

Page 39: ...real Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isol...

Page 40: ...eal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical isola...

Page 41: ...e areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical i...

Page 42: ...areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical is...

Page 43: ...rge areal Earth ampli er with short lines Bridge unused analogue inputs to analogue 0V In the case of terminal names with a number of letters the terminals are bridged on the ampli er If no electrical...

Page 44: ...44 IA VRD UK INDD RH 02 06 Digital Power Ampli er Series VRD350 and VRD355 Installation Manual Parker Hanni n GmbH Co KG Hydraulic Controls Division...

Reviews: