EN
| Operating manual
Maintenance and repair of the dryer
40
WVM 40 -1450
Regular maintenance taskse
The table below shows an overview of the regular maintenance tasks. The individual tasks
are described in detail on the following pages.
Component
Maintenance task
Maintenance interval
daily
monthly
Six-monthly
annually
every 2 years
every 4 years
see page
Entire dryer
Complete visual inspection and function
test.
•
41
Heater
Inspect intake opening for regeneration
gas.
•
41
Switch cabinet
Check that the screw connections and
clamps are secured; tighten if necessary.
(Reduce maintenance intervals in the event
of heavy vibrations.)
•
41
Silencer
Renew silencer every year and after desic-
cant renewal.
•
•
42
Control air fi lter
Inspect control air fi lter and clean or
replace, if necessary.
•
42
Dewpoint trans-
mitter
Renew
•
42
Vacuum pump
Inspect bearing and replace, if necessary
•
44
Dust fi lter
Check dust fi lter for contamination and
clean, if necessary.
•
44
Desiccant
Check desiccant for contamination and
replace, if necessary.
•
44
Preliminary and
afterfi lter (optional)
Please refer to the manuals of the installed fi lters for details on the maintenance
tasks to perform.
When carrying out any maintenance work, please observe the following safety instructions:
Danger!
Working on the dryer when it is switched on and under pressure entails a subs-
tantial risk of injury.
Before starting maintenance work, always shut down the dryer as described on
page „Depressurising and shutting down the dryer“ 37 !
Risk of injury posed by hot surfaces!
The dryer’s surfaces may remain very hot even after it is switched off. Do not
touch hot surfaces!
Wait until the surfaces have cooled down suffi ciently before starting work on
the dryer.
Electric current warning!
Work on the electric system must only be carried out by qualifi ed technical
personnel!
Summary of Contents for Zander WVM 1080
Page 1: ...WVM 40 1450 Adsorption dryer Operating manual Revision 04 06_2018 EN Cod 398H271785 ...
Page 2: ......
Page 55: ......