The minimum speed is always lower and the boosted speed greater than normal speed. When the
speed is changed in any mode other than the maintenance mode, the rotation speed of the
Eximus Jr Unit will change within one minute.
Setting the extract and intake fan rotation ratio
In order to create an underpressure in the house, the rotation ratio of the intake and extract fans
must be adjusted. This is done as follows:
- Push the maintenance mode button (button 4.)
- Push the heating element on/off button (button 3) until code P2 is shown on the
display.
- Push the “+” or “-” buttons until the desired fan rotation ratio is between -30%
and 0% (the factory setting is -20%).
Setting and resetting the maintenance monitor time
The time of the maintenance monitor can be changed when the unit is being installed by pushing
the filter-reset button once. The display now shows the set time. The desired time can be set with
the “+” and “-” buttons. The maintenance monitor time can be set to 2–12 months with one-
month intervals. The factory setting is four months. If no button is pushed within 10 seconds, the
display returns to the basic mode.
After the filter has been cleaned or changed, the maintenance monitor must be reset by pushing
the reset button in the filter compartment twice. The unit must be running when the reset button
is pushed, otherwise the action will not be saved in the memory of the unit.