background image

4838 Reactor Controller

11

c.  All of PID parameters in the group can be ob-

tained from auto-tuning or they can be set 
manually. When manually entering PID values 
into a particular group, the SV for that group can 
be manually entered as well.

Autotuning

1.  Fill the vessel with an amount of liquid which 

well represents the intended process. 

Caution!

Refer to Manual 230M for safety information 

on  the  heating  of  liquids  in  Reactors 

and Pressure Vessels.

2.  If you wish to autotune at different temperatures 

using the four available PID groups proceed with 
step 3, otherwise skip to step 4. 

3.  Press the set key once followed by the return key 

(circular arrow) twice. [

PID0

] will be displayed 

on the screen in the top display. Use the up and 
down arrow keys to change between PID groups 
0, 1, 2 and 3. Press the set key to solidify the 
change. Press the set key again to return to the 
main screen.

4.  Heat the system to the desired temperature us-

ing set point control on the primary temperature 
controller. Let the temperature come to steady 
state which will typically occur 15 to 30 minutes 
after reaching the desired set point depending 
on the size of the reactor.

5.  On the main screen of the controller, press the 

set key. The screen will show [

AT

] on the top 

display and [

OFF

] on the bottom display. Press 

the up arrow to change the lower display to 
[

ON

]. The display will blink, press set to solidify 

the change. Press set again to return to the main 
screen.

6.  As the Autotune starts, the LED indicator under 

AT will blink, and Out 1 will fully engage at-
tempting to heat the reactor 100% power. This 
will continue for a while, and the controller 
will go through a few cycles where it turns the 
power on at 100% and turns it off to see how the 
temperature responds.

7.  A typical Autotune time is half an hour for liquid 

water systems, but it may take longer depending 
on the process. When the process is complete, 
the AT light will stop fl ashing, and the tempera-
ture will settle on the set point.

Temperature Profi les - Ramp and Soak

The 4838 Controller has a programming feature 
which allows more fl exibility when compared to set 
point control. Rather than controlling temperature 
to a single set point, a ramp and soak program may 
be entered to control various soak times, ramp rates 
and set points. Within the programming mode there 
are eight patterns available with each pattern hav-
ing up to eight steps which can be programmed. 
Patterns can be set to repeat and they can be linked 
to other patterns (or the same pattern which allows 
for infi nite program cycles). This allows for up to 64 
unique steps and thousands of possible program 
confi gurations.

To input a ramp and soak:
1.  First set the controller’s Run/Stop [

R-S

] pa-

rameter to Stop [

STOP

]. This will prevent the 

program from automatically starting after the 
program has been entered. You can do this by 
pressing the return key  once and use the arrow 
keys to change the setting to “stop” and press 
the set key to solidify the change.

2.  To enable the ramp and soak control mode, hold 

the set key for approximately three seconds. The 
upper display will change to indicate the Input 
[

INPT

] parameter, and the lower display will 

indicate the temperature sensor type.

3.  Press the return key until the upper display 

indicates the control mode parameter [

CRTL

and the lower display indicates the control 
method (default is PID [

PID

]). Use the arrows 

to change this value to the program [

PROG

setting. The display will blink, and pressing the 
set key will solidify the change.

4.  Press the return key once. The upper display will 

indicate the pattern [

PATN

] parameter and the 

lower display will show the pattern number. The 
pattern parameter defi nes which pattern param-
eters are being viewed in steps 5 - 10. Setting the 
pattern parameter to off [

OFF

] allows you to 

skip the proceeding ramp/soak parameters. Use 
the arrow keys to change the pattern number 
and press the set key to solidify the change.

5.  Press the return key once. The upper display will 

read [

SP00

], where the “00” represents the 

pattern and step number, respectively. The lower 
display will indicate the set point for indicated 
step. The set point can be adjusted using the 
arrow keys then press the set key to solidify the 
change.

Summary of Contents for 4838

Page 1: ...4838 Reactor Controller Operating Instruction Manual...

Page 2: ...ry Switches and Indicators 8 Protective Fuses and Relays 8 High Limit Reset 9 Access to the Controller Cabinet 9 Fuses 9 Instructions for the 4838 Reactor Controller Temperature Control Module 10 Comm...

Page 3: ...h of these controllers and describe the several optional control modules which can be added to these ex pandable units The users should study the instruc tions carefully before using any of these cont...

Page 4: ...4838 Controller There are no user serviceable parts inside the prod uct other than what is speci cally called out and discussed in this manual Advanced troubleshooting instructions beyond the scope of...

Page 5: ...l 4838 Controllers operate with aType J Iron Constantan thermocouple The total resistance of the thermo couple and the lead wires should not exceed 100 ohms If the resistance of the thermocouple circu...

Page 6: ...pera tion within the limits speci ed for that design But in order to preserve the validity of these de signs all temperature and pressure limits must be observed and no attempt should be made to incre...

Page 7: ...troller will not be affected by radiant heat Connections Labeled connections are provided on the rear panel of the controller Heating Only The heating output connector is to be used only with Company...

Page 8: ...When the light comes on the user must nd the source of the problem correct it and then manually reset the system using the high limit reset button on the front of the controller The Main Power Switch...

Page 9: ...imit setting This must be manually reset before heating can occur again On Model 4838 Controllers the high temperature limit is preset at the factory to 375 C for most sys tems On these controllers an...

Page 10: ...the value of the setpoint by adjust ing the heater output The setpoint may be adjusted by doing the following 1 Press the up or down arrow until the lower display shows the desired setpoint The lower...

Page 11: ...p and Soak The 4838 Controller has a programming feature which allows more exibility when compared to set point control Rather than controlling temperature to a single set point a ramp and soak progra...

Page 12: ...set key to solidify the change 11 Press set to return to the main screen Note that the lower display of the main screen has changed to show the program step Note The program will attempt to hold the...

Page 13: ...r knows the expected heat up time It is useful to keep this step 02 separate from step 01 so you can adjust step 01 to match the heat up time The time is zero making this a step function in stead of a...

Page 14: ...involving reactants corrosive to stainless steel the transducer body can be replaced with an isolator of special alloys which will keep the reactants away from the transducer Users should consult wit...

Page 15: ...As an added safety feature there is also a second ary alarm which will trip the High Limit Reset when breached This secondary alarm provides a redun dant high temperature safety cut off which will sh...

Page 16: ...The soft ware is located on the CD at software _ _ _ Com exe 6 Once copied to the PC open the _ _ _ Com exe le No installation is necessary 7 At the main _ _ _ Com program screen select protocol set P...

Page 17: ...se address 3 and an HTM ETLM will use ad dress 4 5 Click the Save button and save a REC le to an appropriate place on the PC When the chart is generated it will write to this le 6 When you return to t...

Page 18: ...Out1 read only Heater output If using a type J or type K thermocouple SP 0 If using an RTD SP 1 Press and hold down SET for 5 sec Operation Mode Select type value Comment InPt J Input type tPUn C Temp...

Page 19: ...ol mode ON OFF MANUAL PID and PID PROG S HC Heat Heat Cool control ALA1 2 Alarm operates when PV value is higher than SV Value ALH setting SALA OFF System alarm CoSH ON Communication write function th...

Page 20: ...nge tP L 0 Lower limit temperature range CTRL ON OFF Control mode ON OFF MANUAL PID and PID PROG S HC Heat Heat Cool control ALA1 6 Alarm operates when PV value is higher than AL1H value SALA OFF Syst...

Page 21: ...ontrol mode Select heating cooling control or dual loop output control Alarm 1 mode setting Alarm 2 mode setting Only available on PrimaryTemperature Controller Alarm 3 mode setting Only available on...

Page 22: ...function is enabled Lower limit alarm 1 This parameter is available only when ALA1 function is enabled Upper limit alarm 2 This parameter is available only when ALA2 function is enabled Lower limit a...

Page 23: ...control mode or Heating and Cooling control cycle Available in PID control mode Control cycle setting of 2nd output group Available in PID control and Dual Loop output control mode P value of 1st 2nd...

Page 24: ...tension wire type J 25 ft A470E6 Thermocouple extension wire type J 30 ft A470E9 Thermocouple extension wire type J 35 ft A470E10 Thermocouple extension wire type J 40 ft A472E4 Thermocouple type J 5...

Page 25: ...s 30 ft covered A1905E10 Pressure harness 35 ft covered A1905E11 Pressure harness 40 ft covered A1906EP02 Transducer 200 psi A1906EP05 Transducer 500 psi A1906EP10 Transducer 1000 psi A1906EP20 Transd...

Page 26: ...ft A470E10 Thermocouple extension wire 40 ft A472E Thermocouple type J 7 1 2 length A472E2 Thermocouple type J 9 1 2 length A472E3 Thermocouple type J 11 1 2 length A472E4 Thermocouple type J 5 1 2 le...

Reviews: