8
Before installing, read these instructions carefully and completely! You must observe the general
safety instructions and the warning symbols with notes in the text.
These instructions are to be passed on to the user after installation (tenant, owner, property ma-
nagement etc.).
Symbols in this manual:
This symbol warns you of an injury risk
This symbol warns you of an injury risk from electricity
Caution!
Installation and assembly work is only to be executed when power supply has been
isolated! The ventilation unit is insulated pursuant to Protection Class II, protective earth
connection is not required!
Attention!
The electrical conection must be installed by authorized skilled staff pursuant to the
valid VDE 0100!
Additional installations and electrical components in this ventilation system are not admissible!
Attention!
This unit must not be operated by children and persons (filter change/cleaning) who
are not able to operate it safely on account of their physical, sensorical or mental capacity or
due to their inexperience or lack of know
-
how.
In the case of fans for exhaust air operation, a functioning back
-
flow of outside air must always
be ensured.
I
nstallation in section 1 in bathrooms and shower rooms is admissible pursuant to VDE 100.
I
nstallation of fan as extractor hood is not admissible
Hints
Operating range:
Temperature range:
-
15°C to +40°C
Usable with relative humidity levels of up to 65% in the interior area (not condensing). The user is
requested to switch off the unit and close the inner screen if the application limits are exceeded.
Ensure fresh air supply by window ventilation.
Safety Instructions
About this manual
EN
The packaging must be sorted before disposal. If you wish to dispose of the ventilation de-
vice, observe the currently applicable regulations. Pursuant to the German Electrical and
Electronic Equipment Act (ElektroG) this device can be returned to your municipal collection
point free of charge.
Disposal
Caution! Any assembly work to the ventilation device may only be carried out after disconnec-
ting all poles of the supply voltage!
Make sure that the supply voltage of all connection lines is voltage
-
free (dead)! (Separation
from the power supply with a minimum contact opening of 3 mm, e.g. electric fuse separating
all poles).
Each electric circuit of this ventilation system must be fitted with a residual current protection
(e.g. FI switch/RCCB)!