TABLE 3-3 TUNE MODE CONFIGURATION PROCEDURE
Depress and release the SCROLL key until tunE is displayed. Use the DOWN key to enter
the Tune mode. Depress and release the SCROLL key to sequence through the parameters
and their values. The upper display will be the parameter code, the lower display will
indicate the parameter value selected. Use the UP and DOWN keys to adjust the values.
After adjusting a parameter, depress the SCROLL key to proceed to the next parameter. Use
the DOWN key to advance to the next parameter code when a parameter code is showing in
the upper display and the lower display is blank. After all selections have been made,
depress the UP key with a parameter code showing in the upper display and the lower display
blank, to exit the mode.
1
Process Alarm
PAL
-9999 to 9999
°
/units
0
(PAL will be seen
if out3=1 or 2)
2
Deviation Alarm
dAL
-3000 to 3000
°
/units
0
(dAL will be seen
if out3=3 or 4)
3
Deviation Band
dbAL
1 to 3000
°
/units
1
Alarm
(dbAL will be seen
if out3=5 or 6)
4
1st Output
Pb1
1 to 3000
°
/units
100
Proportional
Band Width
(Pb1 will not be
seen if out1=1,2)
5
2nd Output
Pb2
1 to 3000
°
/units
100
Proportional
Band Width
(Pb2 will not be
seen if out2=0,1,2,7)
6
Manual Reset
rSt
-1500 to 1500
°
/units
0
7
Automatic Reset
ArS1
0.0 to 100.0 repeats
0.0
Output 1 (Integral)
per minute
8
Automatic Reset
ArS2*
0.0 to 100.0 repeats
0.0
Output 2 (Derivative)
per mintue
9
Rate (Derivative)
rt1
0.0 to 10.0 minutes
0.0
Output 1
10
Rate (Derivative)
rt2*
0.0 to 10.0 minutes
0.0
11
Cycle Time
Ct1
1 to 240 seconds
30
Output 1
(Ct1 will be seen if
out1=3,4,7)
12
Cycle Time
Ct2
1 to 240 seconds
30
Output 2
(Ct2 will be seen
if out2=3 or 4)
(Continued on next page)
STEP
DESCRIPION
DISPLAY
AVAILABLE
FACTORY YOUR
CODE
SETTINGS
SETTING
SETTING