20
battery connector quickly and firmly.
5.
Plug the EBP cable(s) into the battery connector(s) as shown in Figure 13.
Up to four EBPS may be connected to the UPS.
Connect black to black,. Press
the connector tightly together to ensure a proper connection.
To connect a second EBP, unclip the EBP connector on the first EBP and pull
gently to extend the wiring to the EBP connector on the second EBP. Repeat
for any additional EBPS.
6.
Verify that the EBP connections are tight and the adequate bend radius
and strain relief exist for each cable.
Figure13 Typical EBP Installation
7.
Replace the EBP front cover.
To replace the cover, verify that the EBP cables are routed through the EBP
cover knockouts, cover connects with the cover hook near the left side of the
EBP cabinet. Repeat for each additional EBP.
It is the same with the installation of the front cover. (Refer” to UPS
installation”)