Pathfinder Instruments Model TSC-20A  

Conductivity Controller with Alarm 

 

 

OPERATING MANUAL 

 

 
General Description 

 
The 

Model, TSC-20-A 

is a microprocessor programmable controller that accepts a conductivity electrode as an input. Outputs are; 

one on-off relay;3A mechanical contacts and one Alarm relay, 2A contact. The output can be programmed to operate above or 
below the set point; and the alarm is programmed as an absolute value high alarm. The power source is from100 to 240 VAC, 50/ 
60Hz free voltage there is no need to change connections for different voltages. The controller is programmable from the front 
panel via 3 switches, and calibration is done using two front panel adjustments pots. The front panel is a 1/16 DIN, NEMA 4X rated 
and mounting hardware is provided. 

CRU, RU&CE approvals are standard

 

 
Specifications 

 

Measuring Scale Ranges: ………………………….10uS to 75mS

 

Probe Constant: ……………………………………….K= 0.01, K=0.1, K=1.0, K=1.5, K=2.3, K=10

 

Accuracy 

.......................................................± 2% of span 

Output Relay 

.................................................S. P. D. T. Relay 3 Amp @ 115VAC, Resistive Load 

Alarm Relay..

..................................................S. P. S. T. Relay 2 Amp @ 115VAC, Resistive Load 

Power

.............................................................100 to 240 VACS 50/60 Hz @ 3Watts 

Operating temperature range 

.....................-10 to +50ºC 

Storage temperature range 

.........................-20 to +60ºC 

Display 

...........................................................4 Digit red LEDs (Conductivity) 4 Digit green LED's (Set Point) 

Dimensions 

....................................................48 x 48 x 78.8 mm (1/16 DIN) 

 

Memory 

.........................................................Non – volatile 

 

 

 

Page1 

Installation 

A. First Things 

Upon receiving your order of 

TSC-20-A 

controller check to verify that the part number and quantities agree with the enclosed 