At this point we need to stop assembling the heater and test for any possible gas leaks in the
regulator assembly and head to feed line connection. In order to achieve the leak testing we
must attach the twelve-foot hose and couplers to the gas supply. If you are not comfortable
either hooking up the valve at the gas supply line or leak testing the unit you should contact a
licensed plumber, gas technician, or public utility.
©
AEI CORPORATION 2005
14
Step 8:
1) Since there are a variety of possible gas supply
configurations our directions can only be
general in nature.
2) First, shut off the flow of gas to the stub.
3) This can be accomplished at the stub if you
have a shut off on your stub. If not, you will need to shut off the gas at
its source to your stub.
Figure #8
4) Attach the combination coupler/shut off valve onto your ½” gas line.
Your line may be larger than ½” so it must be reduced to ½” in order to
attach the shut-off valve. This is a very safe and convenient system so
please do not try to modify it in any way,
5) Use an approved pipe sealant or Teflon Gas tape to seal the connection
from the stub to the shut-off valve. (See Figure #8)
Step 9:
1) With gas still shut off. Insert one of the 3/8” male nipple fittings at end
of the 12 foot hose into the coupler at the end of the
shut-off valve/coupler.
Figure #9
2) You can engage and disengage the couplers
by just sliding the ring back at the end of the
coupler. The male nipple at the ends of the
hose should insert and disengage easily.
3) The couplers can only work one way. When
the unit is not in use you can leave the hose
attached to the heater or you disengage the
hose set either at the heater or at the fuel
supply or at both points. (See Figure #9) Please try to position the
hose so that it does not present a trip hazard.
Summary of Contents for NPC05
Page 8: ...AEI CORPORATION 2005 8...