54
Wall mount Signal Tower Instruction Manual
8. Operation
●
Diagnostics (08H)
Control Command
Transaction
ID
Protocol
ID
Field
Length
Unit
Identifier
Function
Code
Data
Diagnosis
Sub Cod
*1
Data
*2
00H 03H
00H 00H
00H 06H
00H
08H
00H 00H
00H 00H
*1 Fixed to "00H 00H".
*2 Fixed to "00H 00H".
Response Command
When powered
Transaction
ID
Protocol
ID
Field
Length
Unit
Identifier
Function
Code
Data
Diagnosis
Sub Cod
Data*
00H 03H
00H 00H
00H 06H
00H
08H
00H 00H
00H 01H
* Response Data when powered: 00H 01H
●
Write Multiple Resisters (10H)
Control Command
①
・
Signal Tower: "Tier 1: Light on", "Tier 2: Flashing (slow)", "Tier 3: No change", "Tier 4: Light off"
・
Buzzer: When emit buzzer with "Pattern 2"
Transaction
ID
Protocol
ID
Field
Length
Unit
Identifier
Function
Code
00H 04H
00H 00H
00H 13H
00H
10H
Data
Start
Address
*1
Number of
Registers
*2
Number of
bytes
*3
Register1
Register2
Register3
Register4
Register5
Register6
00H 00H
00H 06H
0CH
01H 01H
01H 02H
00H 00H
01H 00H
00H 00H
01H 02H
*1 To control register addresses, specify "-1" of the start register address.
*2 Specify the number of registers to send.
*3 Specify the number of bytes in the register to send.
Response Command
①
Transaction
ID
Protocol
ID
Field
Length
Unit
Identifier
Function
Code
Data
Start
Address
Number of
Registers
00H 04H
00H 00H
00H 06H
00H
10H
00H 00H
00H 06H