3. Check burner for signs of deterioration or corrosion. Replace burner immediately if any
deterioration, corrosion, or damage is found. If damage to the burner is suspect from improper
combustion settings, be sure to do a combustion check to the factory preferred settings.
The burner may be cleaned with compressed air if any accumulated dust or lint is found. This
must be done with the burner outside of the combustion chamber.
4. Inspect combustion chamber when the burner door is open. Pay careful attention to the door O-
Ring, Braided Rope Gasket, and the door’s insulation/refractory. If any of these show signs of
damage or deterioration; they will need replaced immediately. Note any signs of deterioration or
build-up of deposits on the coils of the heat exchanger. Clean as necessary following the
procedure in
Proper Ignition Electrode Alignment
Proper Ionization Rod Alignment