NUMBER
NUMÉRO
:
P-24872
PAGE 12
FAN HVLS SAFETY CABLES INSTALLATION INSTRUCTIONS
3
DATE (Y/M/D) :
PAR / BY :
DESCRIPTION
RÉVISION / REVISION
TITLE
TITRE :
P/N 203623
DWG P-24872
REVISION
RÉVISION
3
2013-04-11
SAME AS REV 2
P.F.
INSTALLATION OF THE BLADE SAFETY CABLE (#202163):
PASS THE WIRE ALTERNATELY THRU THE HOLES OF THE BLADE
MOUNTING PENTAGON AND THE HOLES OF THE BLADE PINS, OVERLAP
THE WIRE ROPE BY AT LEAST 4-3/4" AND PLACE 3 SADDLE CLIPS AS
ILLUSTRATED.
3/32" SADDLE CLIPS SHOULD BE TIGHTENED TO 4 LB-FT
WARNINGS:
-FOR INDUSTRIAL USE ONLY
-AN ELECTRIC DRIVE MUST BE USED TO CONNECT THE FAN (SOLD SEPARATELY)
P/N
DESCRIPTION
QTY
165710
CABLE 3/32'', 7X7, 13 FT LG
4
202163
CABLE 3/32'', 7X7, 8 FT LG
1
202164
CABLE 1/4", 7X19, 10 FT LG
1
171791
3/32 SADDLE CLIP ZINC PLATED
15
187108
1/4 SADDLE CLIP ZINC PLATED
4
149003
CABLE THIMBLE 3/32 (4x INSTALLED ON 165710)
8
202837
QUICK LINK 3/16"
8
201971
HEX BOLT 3/8-16 NC X 4 1/4" LG Z/P GR 5
2
203412
WASHER 3/8 GR 8
4
110665
NYLON INSERT LOCKNUT 3/8-16 Z/P GR 5
2
169735
1/4" EYE & EYE TURNBUCKLE
4
VIEW B
169735
202837
VIEW A
165710 (4x)
INSTALLATION OF THE FRAME SAFETY CABLE (#202164):
THE WIRE ROPE PASSES OVER THE H-BEAM AND THRU
THE HOLES IN THE VERTICAL TUBES.
SADDLE CLIPS #187108 SHOULD BE INSTALLED WITH
THE SADDLE ON THE "LIVE" OR LONG END OF THE ROPE
AND THE U-BOLT ON THE "DEAD" OR SHORT END OF
ROPE. POSITION THEM THE WAY ILLUSTRATED TO
ENSURE THE MAXIMUM STRENGTH.
1/4" WIRE ROPE CLIPS SHOULD BE TIGHTEN TO 15 LB-FT
IF A DOWN ROD IS INSTALLED, USE THE CABLE
PROVIDED WITH THE DOWN ROD
201971
203412
203412
110665
187108 (4x)
4 3/4" MIN
VIEW C
202163
171791 (3x)
171791 (3x)
149003
INSTALLATION OF THE 4 GUY CABLES (#165710):
SADDLE CLIPS #171791 SHOULD BE INSTALLED WITH THE SADDLE ON THE LIVE OR LONG
END OF THE CABLE AND THE U-BOLT ON THE DEAD OR SHORT END OF THE CABLE.
3/32" SADDLE CLIPS SHOULD BE TIGHTENE TO 4 LB-FT
TIGHTEN THE CABLES UNTIL FRAME IS LEVELED
DO NOT OVER STRESS THE CABLE
IF 5 FT OR 10 FT DOWN ROD IS INSTALLED, USE LONGER GUY CABLES #203994 PROVIDED
WHEN FAN IS LEVELED, ANGLE BETWEEN ROOF AND GUY CABLES MUST NOT EXCEED 45º
VIEW D
3 1/4" MIN
OVERALL DIMENSIONS
48 "
(WITHOUT DOWN ROD)
24 FT WHEN #201259 BLADE SET IS INSTALLED
20 FT WHEN #202359 BLADE SET IS INSTALLED
18 FT WHEN #202360 BLADE SET IS INSTALLED
30-45