background image

 

10 

Push button supply air 
mode 

The supply air mode and the supply air fan are switched on by pushing and locking. 
By pushing again the supply air mode is deactivated again.  

Normal-mode 

Both fans are switched on by pushing and locking.  

Button boost ventilation 
mode /  reset filter runtime 

Function-button for boost ventilation mode: 
Pushing this button activates the boost ventilation with an air volume flow for the 
duration of 15 min which corresponds to position 9 of the rotary knob. After the boost 
ventilation time of 15 min is over, the air-flow returns to the previously suppled air 
quantity in the respectively active operating mode. The boost ventilation mode can be 
terminated any time by pushing this button > 3 seconds. 

 

Function button for reset filter runtime: 
An operating hour counter with a set runtime of 180 d is integrated in the control for 
cyclical filter control. The button boost ventilation mode / reset filter runtime is used to 
reset the filter runtime. Pushing this button > 3 s restarts the filter runtime.  
If a reset of the filter runtime is carried out before expiration of the 180 d by pushing 
the button > 3 s, the reset is acknowledged by 4x quick flashing of the LED-fan-
symbol. 

No reset command is possible during an active boost ventilation mode!

   

Tab. 2: Operating functions external control panel 

2.2.1.2 

Signalling of operating and maintenance modes 

Symbol 

LED-Signalling

 

 

Function / meaning / measure

 

 

 

Both LEDs lights 

Operating mode normal mode (exhaust and supply air) 

 

 

LED extract air 
symbol lights                

Operating mode extract air mode active (extract air only) 

 

 

LED supply air 
symbol lights                

Operating mode supply air mode active (supply air only) 

 

LED fan symbol 
lights                          

Boost-ventilation mode active;  

Boost-ventilation mode is possible in any 
operating mode!

  

 

LED fan symbol is 
flashing                         

Un-occupied mode is active;  

Un-occupied mode is possible in any operating 
mode!

 

 

LED fan-symbol is 
flashing quickly             

Filter runtime expired; carry out filter control or filter change 

Boost ventilation mode cannot be activated as 
long as there is not reset command!

  

Tab. 3: Function assignment of LED-signalling 

 

External control signal 0-10V 

The ventilation device can be operated with an external control signal 0-10 V. A 0-10 V applied analogue signal is 
interpreted as control signal for the fan rotational speed. The externally suppled control voltage is only valid above 
the range of the present scale position of the rotary knob.  

In order to use the whole external 0-10 V – control range, the rotary knob must be in position 1!     

 

Boost ventilation mode with external boost ventilation sensing device 

In most cases, boost ventilation sensing devices are mounted in exhaust air rooms such as bathrooms, W.C.s or 
kitchens in order to activate temporary maximum ventilation in these rooms for fast discharge of increased moisture 
and odours.   
When operating this control element, the functional properties and visualisations described for the boost ventilation 
mode are generated. The boost ventilation mode is started again at each activation and interrupts the current 
operating mode for the duration set. Following this, the device switches back to the previously active operating mode. 

Summary of Contents for CLIMOS F 200 Eco

Page 1: ...Version 1 1_08 2019 EN...

Page 2: ...ut prior notification The information contained in these documents is the property of PAUL W rmer ckgewinnung GmbH The publication whether partially or completely requires the written consent of PAUL...

Page 3: ...gnalling of operating and maintenance modes 10 External control signal 0 10V 10 Boost ventilation mode with external boost ventilation sensing device 10 Maintenance by the operator 11 Replacement of t...

Page 4: ...ied personnel 24 Inspecting and cleaning the heat exchanger 25 Visualising of operating modes 29 Technical desciption 30 Designs layout air connection 30 Technical specification 30 Dimensional sketch...

Page 5: ...cial regulations and guidelines Knowledge of and compliance with this document including all safety instructions Unless otherwise stated in this manual only a recognized qualified person is authorized...

Page 6: ...ient conditions not permanently 70 rh at 22 C The acceptable temperature range for the air being moved is between 20 C and 40 C The unit must not be installed in rooms subject to explosion hazards Whe...

Page 7: ...children s rooms For heat recovery the CLIMOS is equipped with a membrane moisture heat exchanger enthalpy exchanger which due to its physical properties is not only able to transfer heat but also moi...

Page 8: ...n the side of the casing next to the electrical connections The type plate must be permanently attached to the product Frost protection The CLIMOS is equipped with an automatic frost protection which...

Page 9: ...symbol with the red LED signals the respective operating mode depending on the function 2 2 1 1 Operating functions control panel Description Explanation Positioning rotary knob Un occupied mode inter...

Page 10: ...ir LED extract air symbol lights Operating mode extract air mode active extract air only LED supply air symbol lights Operating mode supply air mode active supply air only LED fan symbol lights Boost...

Page 11: ...ong term Replacement of the filter The plant must not be operated without filter During filter replacement and maintenance work the ventilation device must be switched off Two high quality original fi...

Page 12: ...ment next to the recessed grip must point in the same direction Fig 7 Insertion of the new filter ISO ePM1 60 F7 filters must be inserted into the filter compartment of the outside air connection depe...

Page 13: ...household garbage For this kind of disposal please obtain information on the possibilities of reuse of components or the eco friendly treatment of the materials from you community 3 Hints for qualifi...

Page 14: ...eight of the CLIMOS is 30 kg and the secure fixing possibility using the mounting brackets If the fixing is made at a wooden or lightweight construction we recommend the die insertion of a vibration d...

Page 15: ...the mounting position wall mounted horizontally the mounting is made horizontally at the wall surface in the slotted holes 38x10 mm of the 4 mounting brackets with suitable fixing elements depending...

Page 16: ...xhaust air connection for the construction types A or B must always be located at the top Fig 14 Mounting position inclined wall horizontally Mounting position inclined wall vertically In case of the...

Page 17: ...a way that they are vapour diffusion tight In the event that a low point is unavoidable when installing the exhaust air duct from the device s exhaust air stub to the exhaust air outlet a connection...

Page 18: ...cable gland M16 3 7 4 Circuit diagram CLIMOS F 200 Eco Comfort Tab 4 Assignment of the electrical connections Connection control panel 3 3 1 1 Connecting of the connection cable to the control panel T...

Page 19: ...board 1 Disconnect the CLIMOS from the power supply 2 If applicable pull the red design filter covers A out of the casing cover s holder 3 Open the quarter turn locks B by turning the captive screw by...

Page 20: ...e and remove the cable for potential equalisation from the flat plug of the control system casing Fig 23 Screws D for fastening the control system casing 6 Push the control system casing in the direct...

Page 21: ...ws Fig 25 Removal of the control system casing in direction heat exchanger Fig 26 Removal of the control system casing above 8 Guide the cable through one of the two rubberised grommets F of the contr...

Page 22: ...fasteners of the control system casing into the keyholes E Fig 29 Establishment of the keyhole connection 11 Place the cables into the free space between the control system casing and the EPP modules...

Page 23: ...al which is generated by one or several sensors The connection between the sensor module and the connection terminal of the operating panel is made with the cable prescribed for the transmission of th...

Page 24: ...nt of a lower fan output or restriction of the volume flow in the pipeline installation of a throttle flap or throttle foam insert Readjustment of the valves Locking of the adjusted positions of the v...

Page 25: ...n check list B Inspecting and cleaning the heat exchanger In order to do so proceed as follows 1 Disconnect the CLIMOS from the power supply 2 If applicable pull the red design filter covers A out of...

Page 26: ...C from the device 5 Pull the retaining clamps D 4x out of the EPP foam modules in vertical position Fig 37 Retaining clamps D for form fit fastening of the EPP foam modules 6 Push each of the fan boxe...

Page 27: ...point of sectioning Fig 39 Shortening of the EPP connection stub at the set point of sectioning of the circumferential groove H After having finished the maintenance work all disconnected air ducts m...

Page 28: ...any aggressive or dissolvent detergents For drying position the heat exchanger in such a way that existing residual water can run out of the openings Let the heat exchanger run completely dry before r...

Page 29: ...on Visualising of operating modes The control unit is equipped with 3 LEDs for signalling of operating modes The following operating conditions are shown with LED signalling LED Signalling Condition c...

Page 30: ...load 110 W 810 W without with preheater Protection class I Degree of protection IP 30 Limitations of use 20 to 40 C Assembly site Frost free interior area Ambient conditions 70 rh at 22 C Installatio...

Page 31: ...se note The numerical values of the p characteristic curve which are illustrated in the chart indicate the power consumption in W in the respective operating points without activated preheater Tab 13...

Page 32: ...32 Dimensional sketch Fig 44 Dimension drawing...

Page 33: ...33 Circiut diagram CLIMOS Eco series Fig 45 Terminal assignment CLIMOS Eco...

Page 34: ...ter change cycle 90 days Quarter Year I II III IV 20 20 20 20 20 20 20 20 20 20 2 Clean extract air prefilter filter in extract air valves change approx every 2 months Quarter Year I II III IV 20 20 2...

Page 35: ...s no Are the control devices and control units functional yes no 3 Air duct heat insulation Is the device cleaned if required Is the testing in place If required refer to VDI 6022 for cleaning yes no...

Page 36: ...anned There is an option to clean yes no yes no yes no 5 Exhaust air line There is an option to clean yes no 6 Exhaust air ventilator There is an option to clean yes no 7 Control unit and control devi...

Page 37: ...ean approx days used Very dirty Supply Air Ventilator stage No Room Description Project Date Measurement Data m h m s m h m s Exhaust Air Ventilator stage No Room Description Project Date Measurement...

Page 38: ...38 Product fiche...

Page 39: ...ion plant conforms to the installation of the plant and to the model identifier of the product data sheet The product label shows the following information from the product data sheet energy efficienc...

Page 40: ...dical equipment Radio frequency disturbance characteristics Limits and methods of measurement Directive 2009 125 EC of the European Parliament and of the Council of 21 October 2009 in view of the requ...

Page 41: ...Version 1 1_08 2019 EN PAUL W rmer ckgewinnung GmbH August Horch Str 7 08141 Reinsdorf Germany Tel 49 0 375 30 35 05 0 Fax 49 0 375 30 35 05 55 info paul lueftung de www paul lueftung de...

Reviews: