14
Fig 8: Distances in mm to adjacent surfaces
For the CLIMOS the following mounting positions are possible:
•
ceiling-hanging or lying (horizontally)
•
wall-mounted (horizontally or vertically)
•
inclined wall (horizontally or vertically)
The exhaust air connection
must always be located at the top!
Mounting
Preparations
At first, mount at the long sides of the CLIMOS 2 pieces of the provided mounting brackets each with 4 cross-head
screw each.
Fig 9: Mounting brackets
At first, check the necessary load capacity of the respective fixing surface (own weight of the CLIMOS is 30 kg) and
the secure fixing possibility using the mounting brackets. If the fixing is made at a wooden or lightweight construction,
we recommend the die insertion of a vibration-damping distance washer for each mounting bracket.
Mounting position ceiling-hanging
In case of the mounting position ceiling-hanging, the mounting is made horizontally at the ceiling surface in the
slotted holes (38x10 mm) of the 4 mounting brackets with suitable fixing elements depending on the ceiling
construction.
If the CLIMOS is to be mounted in an intermediate ceiling, we recommend the use of the product-related drywall
inspection flap in the suspended ceiling. The distance between the lower edge of the raw ceiling and the lower edge