Commissioning
Readiness for operation
The unit is ready for operation once all the requirements of the safety regulations and
installation conditions have been met. In particular, this means ensuring that the ventilation tube
material is clean and that all the ventilation technology components required to operate the system
are present, properly installed and ready for operation.
Check all the safety-related components and carry out a function test.
Adjusting the air volume flow
Once you have checked that the FOCUS unit is ready for operation, you can commission it as described below.
Diagram 1 shows the scale for the available air volume flow in relation to the rotary knob positioning. As per the
system design rules, the nominal ventilation must equal the total outdoor air volume flow. This nominal air volume
flow must correspond to a rotary knob position according to the illustration of the control unit.
Fig. 25: Diagram 1, fan speeds parametrisation
Fig. 26: Diagram 2, assignment of volume flow ranges
Adjusting the valves
At the start of volume flow measurement, make sure that the supply air and extract air valves are
open as wide as possible.
•
Set the fans to the nominal air volume flow
•
Adjust the valve orifices, throttle valves or throttle foam inserts
•
Measure the volume flows at the outlets using a volume flow hood and flow meter (see air volume protocol)
•
Readjust the valves
•
Lock the valves, shutters and throttles in their adjusted positions
•
Record the set air volumes and all other settings in the documentation intended for this purpose
Ar
ea of
1s
t s
cal
in
g s
eg
men
t
Sc
al
ing s
egm
ent
Volume flow [m
3
/h]
Volume flow range for
constant operating mode
Volume flow range for intermittent
operating mode
Volume flow [m
3
/h]
Summary of Contents for FOCUS 200 Base
Page 1: ...Translation of the original instruction manual Heat Recovery Unit FOCUS 200 Base...
Page 30: ...30 Dimensions Fig 33 Dimensional drawing...
Page 31: ...31 FOCUS 200 Base terminal scheme Fig 34 Terminal assignment terminal plan...
Page 36: ...36 PDE Manual_Focus 200 Base_V1 1 V1122 DE Subject to change...