Error handling
44
11.2
Error temperature sensor
Operating temp.
T
oper
(°C)
Resistance
R
25
(k
)
-25
129,30
-20
96,36
-15
72,50
-10
55,05
-5
42,16
0
32,56
5
25,34
10
19,87
15
15,70
20
12,49
25
10,00
30
8,059
35
6,535
Tab. 6: Resistance value
Change fan slave T1-T4
or BUS thermostat T5-T7
Sensor
connected
according to circuit
diagram?
Error temperature sensor
T1 / T2 / T3 / T4 / T5 / T6 / T7
Yes
Mount sensor or
check settings
Yes
No
O.K.
Check
resistance
(tab. 6)
O.K.?
Change
the sensor
No
WARNING!
Do not touch the board
for under 230 V power
supply live components!