4 Assembly and installation [specialist]
2020/04
9932073x-mub-en – V14
15
1.
Take off the thermometer handles
(A-2, F-2) and remove the insulating
front shell of the HeatBloC
®
.
2.
Unscrew the nuts on the lower
connections of the HeatBloC
®
and
take out the sealing rings.
3.
Flip the two nuts over the flanges.
4.
Insert the sealing rings into the nuts.
5.
Put the HeatBloC
®
onto the two nuts.
6.
Tighten the nuts.
Take care that the nuts do not get
jammed and that the sealing rings
do not slip.
7.
Connect the HeatBloC
®
to the
installation. The installation to the
piping must be carried out without
any tension.
8.
Connect the pump.
9.
Mount the pipe contact thermostat
and the sensor (A-3) at the flow pipe.
10.
Carry out the pressure test and check
all thread connections.
11.
Mount the insulating front shell and
the thermometer handles (A-2, F-2).
Flange
(top view)
Nut
1
2
3
Flange
(side view)
Sealing ring