4 Assembly and installation [specialist]
12
99453x0333x-mub-en – V02
2017/02
4
Assembly and installation [specialist]
The HeatBloC MC can be mounted directly to the wall or on a wall bracket set.
NOTICE
Damage to property!
The location of installation must be dry, load-carrying, frost-proof and protected against
ultraviolet radiation in order to prevent material damage of the installation.
4.1
Installation and commissioning of the HeatBloC
NOTICE
Verify if the grounding cable holds securely in place at the differential pressure sensor!
The ground lug points in the direction of the banderole.
1.
Remove the station from the packaging.
2.
Determine the location of installation.
3.
Drill two holes. They must have a distance of
45 mm.
4.
Insert appropriate wall plugs. Please note that the
enclosed wall plugs are only adapted for full brick
masonry.
5.
Screw the stair bolts in such that exactly 25 mm
of the bolts stick out of the wall (see figure on the
left).
6.
Push the enclosed spacer (K) onto the stair bolt.
7.
Push the HeatBloC onto the stair bolt.
8.
Fix the HeatBloC on the stair bolts with the
enclosed washers and nuts.