4 Commissioning [specialist]
2016/05
997655910x-mub-en
–
V07
17
WARNING
Risk to life and limb due to electric shock!
Check if the sensors and pumps are properly connected to the controller
and if the controller housing is closed.
Only then, the mains plug of the controller can be plugged into a socket.
15.
Connect controller (not part of delivery) to the
mains and set the solar circuit pump in the
manual mode to Max. according to the controller
instructions. Let the pump of the solar circuit
run at maximum revolution speed for at least
15 minutes.
16.
Vent the solar installation several times at the
vent plug of the Airstop until the solar fluid exits
without bubbles (see page 13).
If necessary, increase the system pressure to
the operating pressure.
17.
Remove the hoses of the flush and fill station
and screw the sealing caps onto the fill and drain
valves.
The sealing caps only serve to protect the valves
against dirt. They are not designed to take up
high system pressures. The ball valves must
be closed to guarantee tightness.