background image

2. Set temperature rise.

Furnace must operate within range of temperature rise
specified on the unit rating plate. Determine the air tem-
perature rise as follows.

a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
"see" heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.

WARNING:

Disconnect the electrical power before

changing the speed tap. A failure to follow this warning
can cause personal injury.

d. To change blower motor speed selections for heating

mode, remove blower motor lead from control board
HEAT terminal. (See Fig. 9.) Select desired blower
motor speed lead from 1 of the other terminals and
relocate it to HEAT terminal. See Table 9 for lead color
identification. Reconnect original lead on SPARE termi-
nal.

CAUTION:

Recheck temperature rise. It must be within

limits specified on unit rating plate. Recommended op-
eration is at midpoint of rise or above.

3. Set thermostat heat anticipator.

The thermostat heat anticipator must be set to match the
amp draw of the electrical components in the R-W circuit.
Accurate amp draw readings can be obtained at thermostat
subbase terminals R and W. Fig. 13 illustrates an easy

TABLE 7—GAS RATE CU FT/HR

SECONDS

FOR 1

REVOLUTION

SIZE OF

TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF

TEST DIAL

1

cu ft

2

cu ft

5

cu ft

1

cu ft

2

cu ft

5

cu ft

10
11
12
13
14

360
327
300
277
257

720
655
600
555
514

1800
1636
1500
1385
1286

50
51
52
53
54

72
71
69
68
67

144
141
138
136
133

360
355
346
340
333

15
16
17
18
19

240
225
212
200
189

480
450
424
400
379

1200
1125
1059

100
947

55
56
57
58
59

65
64
63
62
61

131
129
126
124
122

327
321
316
310
305

20
21
22
23
24

180
171
164
157
150

360
343
327
313
300

900
857
818
783
750

60
62
64
66
68

60
58
56
54
53

120
116
112
109
106

300
290
281
273
265

25
26
27
28
29

144
138
133
129
124

288
277
267
257
248

720
692
667
643
621

70
72
74
76
78

51
50
48
47
46

103
100

97
95
92

257
250
243
237
231

30
31
32
33
34

120
116
113
109
106

240
232
225
218
212

600
581
563
545
529

80
82
84
86
88

45
44
43
42
41

90
88
86
84
82

225
220
214
209
205

35
36
37
38
39

103
100

97
95
92

206
200
195
189
185

514
500
486
474
462

90
92
94
96
98

40
39
38
38
37

80
78
76
75
74

200
196
192
188
184

40
41
42
43
44

90
88
86
84
82

180
176
172
167
164

450
439
429
419
409

100
102
104
106
108

36
35
35
34
33

72
71
69
68
67

180
178
173
170
167

45
46
47
48
49

80
78
76
75
73

160
157
153
150
147

400
391
383
375
367

110
112
116
120

33
32
31
30

65
64
62
60

164
161
155
150

Fig. 11—Redundant Automatic Gas Control Valve

A95618

MANIFOLD
PRESSURE  TAP

GAS
PRESSURE
REGULATOR
ADJUSTMENT

INLET
PRESSURE  TAP

ON AND
OFF SWITCH

Fig. 12—Burner Flame

A89020

BURNER  FLAME

BURNER

MANIFOLD

TABLE 8—CANADIAN ORIFICE SIZE

GAS

SEA LEVEL

0—2000 FT

HIGH ALTITUDE

2000—4500 FT

Natural

43

44

Propane

54

55

TABLE 9—SPEED SELECTOR

COLOR

SPEED

FACTORY-

ATTACHED TO

Black

High

Cool

Yellow (When

present)

Medium-High

Spare

Blue

Medium-Low

Heat

Red

Low

Spare

White

Common

COM

—13—

Summary of Contents for 480BAV Upflow

Page 1: ...the National Standard of Canada CAN CGA B149 1 and 2 M95 Natural Gas and Propane Installation Codes NSC NGPIC Wear safety glasses and work gloves Have fire extin guisher available during start up and...

Page 2: ...E VENT CONN SHIP WT LB 024045 14 3 16 12 9 16 12 11 16 4 122 036045 14 3 16 12 9 16 12 11 16 4 124 024065 14 3 16 12 9 16 12 11 16 4 132 036065 14 3 16 12 9 16 12 11 16 4 134 042091 17 1 2 15 7 8 16 4...

Page 3: ...tion details refer to the applicable instruction literature NOTE Remove all shipping brackets and materials before operating the furnace I LOCATION A General CAUTION Do not install furnace in a corros...

Page 4: ...s and screens must be considered If the free area of a louver or grille design is unknown it may be assumed that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent...

Page 5: ...casing side and into the filler strip to secure it in place Filter should rest on the top of the filler strip when installed WARNING Never operate unit without a filter or with filter access door rem...

Page 6: ...Apply joint compound pipe dope sparingly and only to the male threads of each joint The compound must be resistant to the action of propane gas An accessible manual shutoff valve MUST be installed up...

Page 7: ...ode indicator light will flash rapidly and the furnace will not operate B 24 v Wiring Make field 24 v connections at the 24 v terminal strip See Fig 9 Connect terminal Y as shown in Fig 8 for proper c...

Page 8: ...HACR TYPE CKT BKR AMPS Maximum Minimum 024045 115 60 1 127 104 6 0 14 47 15 036045 115 60 1 127 104 8 3 14 34 15 024065 115 60 1 127 104 5 9 14 47 15 036065 115 60 1 127 104 8 7 14 32 15 042091 115 6...

Page 9: ...energizing the gas valve stopping gas flow to the burners The blower motor and EAC remain energized for 135 sec h Post purge The inducer motor remains energized 5 sec after the burners are extinguish...

Page 10: ...OMPONENT TEST TWIN TERMINAL TRAN TRANSFORMER 115VAC 24VAC JUNCTION UNMARKED TERMINAL PCB TERMINAL FACTORY WIRING 115VAC FACTORY WIRING 24VAC FIELD WIRING 115VAC FIELD WIRING 24VAC CONDUCTOR ON PCB FIE...

Page 11: ...llows a Momentarily jumper TEST and Com terminals until LED goes off b LED will display previous fault 4 times c Inducer motor operates for 10 sec then stops d Hot surface ignitor is energized for 15...

Page 12: ...0 62 0 64 0 66 0 68 0 70 0 72 Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press Orf No Mnfld Press...

Page 13: ...E CU FT HR SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 13 14 360 327 300 277 257 720 655 600 555 514...

Page 14: ...erature c After normal start up allow furnace to operate for 2 minutes then block flue outlet 100 percent Furnace should cycle off within 2 minutes d Remove blockage and reconnect vent pipe to furnace...

Page 15: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Page 16: ...1996 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 16 480b454 Catalog No PA 3348 009...

Reviews: