79
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
!
WARNING
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger
CANNOT be serviced or inspected without complete removal of
the heat exchanger assembly. Detailed information on heat
exchanger removal can be obtained from your Distributor.
WINTERIZATION
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit component or
property damage.
If the furnace is installed in an unconditioned space where the
ambient temperatures may be 32
F (0
C) or lower, freeze
protection measures must be taken to prevent minor property
or product damage.
CAUTION
!
Since the furnace uses a condensing heat exchanger, some water
will accumulate in the unit as a result of the heat transfer process.
Therefore, once it has been operated, it cannot be turned off and
left off for an extended period of time when temperatures will
reach 32
F (0
C) or lower unless winterized. Follow these
procedures to winterize your furnace:
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
furnace and other property damage.
Do not use ethylene glycol (automotive antifreeze coolant or
equivalent). Failure of plastic components may occur.
CAUTION
!
1. Obtain propylene glycol (RV/swimming pool antifreeze or
equivalent).
2. Turn off gas and electrical supplies to your furnace.
3. Remove furnace control door.
4. Remove the top unused rubber plug from the port on the
collector box opposite the condensate trap. See Fig. 67.
5. Connect a field supplied 3/8
−
in. (9.5
−
mm) ID tube to the
open port on the collector box.
6. Insert a field supplied funnel into the tube.
7. Pour one quart (liter) of anti
−
freeze solution into the funnel/
tube. Antifreeze should run through the inducer housing,
overfill condensate trap and flow to an open drain.
8. Replace the rubber plug in the port on the collector box.
9. Remove the middle unused rubber plug from the port on the
collector box opposite the condensate trap. See Fig. 67.
10. Repeat Steps 5 through 8.
11. If a condensate pump is used, check with pump manufacturer
to verify pump is safe for use with antifreeze used. Allow
pump to start and pump anti
−
freeze to open drain.
12. Replace main door.
13. When furnace is re
−
started, flush condensate pump with clear
water to check for proper operation before re
−
starting furnace.
14. Propylene glycol need not be removed before re
−
starting
furnace.
2-1/2-in.
(64.4)
1-1/4-in.
(31.8)
A11405
Fig. 65
−
Igniter Position
−
Top View
2
ï
in.
2.5 mm
3/8
ï
in.
3/16
ï
in.
+0.8
ï
1.5 mm
50 mm
9.6 mm
4.6 mm
1/10
ï
in.
+ 1/32
ï
1/16
ï
in.
L12F041
Fig. 66
−
Igniter Position
−
Side View
A11392
Fig. 67
−
Priming Condensate Trap
PG92S*S