RESTRICTIONS IN HORIZONTAL CONFIGURATIONS

HORIZONTAL LEFT TOP
RETURN NOT PERMITTED
FOR ANY MODEL.
SEE TABLE BELOW.

RETURN

AIR

*RETURN 

AIR

*HORIZONTAL LEFT BOTTOM RETURN
NOT PERMITTED FOR ALL MODELS.
SEE TABLE BELOW.

SUPPLY

 AIR

1

2

3

*

A14006

INPUT*

CASING

WIDTH

INCHES

HORIZONTAL LEFT RETURN AIR CONNECTIONS

CONNECTION AT

1 ONLY

CONNECTION AT

2 ONLY

CONNECTION AT

3 ONLY

COMBINATION OF 1 & 2

40,000

14 3/16

YES

YES

NO

YES

17 1/2

YES

YES

NO

YES

60,000

14 3/16

YES

YES

NO

YES

17 1/2

YES

NO

NO

YES

80,000

17 1/2

YES

YES

NO

YES

21

YES

YES

NO

YES

100,000

21

YES

YES

NO

YES

120,000

24 1/2

YES

YES

NO

YES

INPUT*

CASING

WIDTH

INCHES

HORIZONTAL RIGHT RETURN AIR CONNTECIONS

CONNECTION AT

1 ONLY

CONNECTION AT

2 ONLY

CONNECTION AT

3 ONLY

COMBINATION OF 1 & 2

40,000

14 3/16

YES

YES

NO

YES

17 1/2

YES

YES

NO

YES

60,000

14 3/16

YES

YES

NO

YES

17 1/2

YES

YES

NO

YES

80,000

17 1/2

YES

YES

NO

YES

21

YES

YES

NO

YES

100,000

21

YES

YES

NO

YES

120,000

24 1/2

YES

YES

NO

YES

NOTE

: Not all models may be available in all casing sizes shown in the table above.

PG92SC

S

Summary of Contents for PG92SCS

Page 1: ...tor S 4 way multipoise furnace S Hot surface ignition S LED diagnostics and self test feature S Stores fault codes during power outages S Adjustable heating air temperature rise S Adjustable cooling airflow S Approved for Manufactured Housing Mobile Home applications with MH accessory kit S Approved for Twinning applications 48060 through 60120 sizes only S Certified to leak 2 or less of nominal a...

Page 2: ...an ten years of field proven performance and success These innovations paired with the continuation of a crimped no weld seam create an efficient robust design for this essential component The condensing heat exchanger a stainless steel fin and tube design is positioned in the furnace to extract additional heat Stainless steel coupling box componentry between heat exchangers has exceptional corros...

Page 3: ...885 1490 1970 2050 Cooling Capacity tons 400CFM ton 2 5 3 5 4 0 4 5 3 5 5 0 5 0 350CFM ton 2 5 4 0 4 5 5 0 4 0 5 5 5 5 Direct Drive Motor Type Permanent Split Capacitor PSC Direct Drive Motor HP 0 3 5 0 5 0 75 0 5 1 1 Motor Full Load Amps 4 6 7 9 7 4 7 9 6 5 11 1 11 1 RPM Range 500 1150 Speed Selections 4 4 5 5 4 4 4 Blower Wheel Dia x Width in 11 x 7 11 x 8 11 x 8 11 x 10 11 x 10 11 x 10 11 x 11 ...

Page 4: ... 5 95 AFUE 6 96 AFUE 7 97 AFUE 24 800 CFM 30 1000 CFM 36 1200 CFM 42 1400 CFM 48 1600 CFM 54 1800 CFM 60 2000 CFM 66 2200 CFM 0 5 ESP Example of a Model Number A12375 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS VALVE MAIN LIMIT SWITCH BEHIND GAS VALVE REPRESENTATIVE DRAWING ONLY SOME MODELS MAY VARY IN APPEARANCE ELECTRICAL JUNCTION BOX IF REQUIRED LOCATION MAY VARY OPERAT...

Page 5: ...o Nat KGBPN42011SP D D D D D D D Gas Orifice Kit 42 Nat Gas LH32DB207 D D D D D D D Gas Orifice Kit 43 Nat Gas LH32DB202 D D D D D D D Gas Orifice Kit 44 Nat Gas LH32DB200 D D D D D D D Gas Orifice Kit 45 Nat Gas LH32DB205 D D D D D D D Gas Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D Gas Orifice Kit 47 Nat Gas LH32DB078 D D D D D D D Gas Orifice Kit 48 Nat Gas LH32DB076 D D D D D D D Gas Orific...

Page 6: ...0 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 048100 SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1535 1480 1435 1380 1325 1260 1180 1095 1010 910 Blue 3 3 0 367 1300 1255 1205 1160 1100 1035 970 905 810 730 Red 3 2 0 445 1110 1055 1005 955 890 835 770 690 610 535 060100 BOTTOM or TWO SIDES 4 5 Black 5 0 394 2270 2...

Page 7: ...Temp C Unit Size 40 000 BTUH 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76 38 51 64 76 7 6 1 6 1 6 1 6 1 15 2 13 7 6 1 18 3 15 2 6 1 9 1 9 1 7 6 6 1 22 9 19 8 18 3 6 1 25 9 22 9 19 8 18 3 0 1 5 1 5 6 1 7 6 6 1 6 1 9 1 7 6 4 6 4 6 3 0 3 0 6 1 12 2 9 1 7 6 6 1 13 7 12 2 9 1 29...

Page 8: ... 40 000 Outlet choke required under 10 ft TEVL 60 000 80 000 100 000 120 000 140 000 Altitude meters Pipe Dia mm 38 51 64 38 5 64 76 38 51 64 76 102 51 64 76 102 64 76 102 64 76 102 0 610 6 26 57 6 5 31 54 61 2 16 40 54 61 6 25 54 61 3 23 57 1 5 21 48 611 914 4 5 24 53 29 51 57 3 15 38 51 57 5 23 51 57 21 54 N A 18 42 915 1219 22 49 5 27 48 54 36 48 53 48 54 1 5 20 51 36 1220 1370 3 20 47 26 46 52...

Page 9: ...eters of PVC ABS pipe VERIFY FROM VENT MANUFACTURER S INSTRUCTIONS Can this application use 60 mm O D polypropylene vent piping If not what size piping can be used Measure the required linear length of air inlet and vent pipe insert the longest of the two here 100 ft Use length of the longer of the vent or air inlet piping system Add equiv length of 3 90º long radius elbows use the highest number ...

Page 10: ...PLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sides of Supply Plenum 1 in 25 mm Sides 0 0 mm Vent 0 0 mm Top of Furnace 1 in 25 mm Recommended Consult your local building codes COMBUSTION AIR PIPE FOR NON DIRECT 1 PIPE VENT APPLICATION FIELD SUPPLIE...

Page 11: ... 1 2 YES YES NO YES 60 000 14 3 16 YES YES NO YES 17 1 2 YES NO NO YES 80 000 17 1 2 YES YES NO YES 21 YES YES NO YES 100 000 21 YES YES NO YES 120 000 24 1 2 YES YES NO YES INPUT CASING WIDTH INCHES HORIZONTAL RIGHT RETURN AIR CONNTECIONS CONNECTION AT 1 ONLY CONNECTION AT 2 ONLY CONNECTION AT 3 ONLY COMBINATION OF 1 2 40 000 14 3 16 YES YES NO YES 17 1 2 YES YES NO YES 60 000 14 3 16 YES YES NO ...

Page 12: ... 5 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric Vent Kit A93086 A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the ...

Page 13: ...ND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING Connect Y Y2 terminal as shown for proper operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be replaced use same type or equivalent wire 208 230 OR 460 VOLT THREE PHASE 208 230 VOLT SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NO...

Page 14: ...TE ALL DIMENSIONS IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters a For 800 CFM 16 in 406 mm round or 14 1 2 x 12 in 368 x 305 mm rectangle b For 1200 CFM 20 in 508 mm round or 14 1 2 x 19 1 2 in 368 x 49...

Page 15: ...n mm X ________ in mm An accessory highly efficient Media Filter is available as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted steel Draft Inducer Motor Draft inducer motor shall be single speed PSC design Primary Heat Exchangers Primary heat exchangers shall be 3 Pass corrosion resistant aluminized steel of fold and crimp sectional design and ...

Page 16: ...s D 7310 W Morris St D Indianapolis IN 46231 Edition Date 12 14 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No SS PG92SCS 03 Replaces SS PG92SCS 02 PG92SCS ...

Reviews: