1.4. SPECIFICATIONS
1.4.1. Power
Supply
20 to 28 VAC/DC
1.4.2. Power
Consumption
Standard Unit: 192mA at 24VAC
113mA at 24VDC
Full Options:
417mA at 24VAC
229mA at 24VDC
1.4.3. Accuracy
±0.25% full scale (Standard)
±0.10% full scale (Optional)
1.4.4. Temperature
Input
Options
0-10VDC
4-20mA
1.4.5. External Flow Input Options
0-10VDC
4-20mA
1.4.6. Economizer Override Input Options
0-10VDC
4-20mA
1.4.7. System Start Input
Dry Contact
1.4.8. Process (MT2 Measured / Total) Output Options
0-5VDC
0-10VDC
4-20mA (700
Ω
maximum load)
1.4.9. Controller Output Options
0-5VDC
0-10VDC
4-20mA (700
Ω
maximum load)
1.4.10. High/Low Alarm Relay Outputs
Two single (1 form C) dry contacts rated for:
5 amps at 30VAC/dc
10 amps at 120VAC