MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
8
Revision Level 002
4. INPUT/OUTPUT SET-UP
The MicroTrans
II
has been configured and calibrated at the factory for the specific application. Refer to
the MicroTrans
II
Set-Up label located on the left side of unit to verify correct Input/Output configuration
for the application. If input or output configuration changes are required refer to the tables in the
sections below and the figure in Section 3.1.
4.1. TEMPERATURE
INPUT (OPTION)
To change the input configuration, set the
TMP
switch as follows:
Temperature Input
AINP (TMP)Selection
4-20mA mA
0-10VDC V
4.2.
EXTERNAL AIRFLOW INPUT
To change the input configuration, set the
SP
switch as follows:
Setpoint Input
AINP (SP) Selection
4-20mA mA
0-10VDC V
4.3. ECONOMIZER
OVERRIDE INPUT (OPTION)
To change the input configuration, set the
ECO
switch as follows:
Economizer Override Input
AINP (ECO) Selection
4-20mA mA
0-10VDC V
4.4. PROCESS
OUTPUT
To change the output configuration, set the
PRO
switch as follows:
(Note: See section 4.7 for voltage level select)
Process Output
AOUT (PRO) Selection
4-20mA mA
0-10VDC V
0-5VDC V
4.5. TEMPERATURE
OUTPUT
To change the output configuration, set the
TMP
switch as follows:
(Note: See section 4.7 for voltage level select)
Temperature Output
AOUT (TMP) Selection
4-20mA mA
0-10VDC V
0-5VDC V