MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
16
Revision Level 002
Min Value
(-000)
Max Value
(000)
Op Range Outside
Allowable Value.
Op Range Will be
Reset to the MAX
F.S. Value
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Min &
Max Temperature
value and pressing the
Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(6,000 - 12,000)
(ACFM)
Enter Value
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Temperature Range Example-
Temp. Range
Min Value
(-000)
Max Value
(000)
Accepted
Temp. Range
5.4.4. Temperature
Input
The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in
the Fixed Value Menu (see Section 5.4.5) is used. The Standard Fixed Value is 68
˚
F. If Variable is
selected an external temperature input signal is required (see Sections 5.4.1 through 5.4.3). If Net is
selected, the temperature input signal is obtained through network communications. The Net option is
only available if one of the communication options is ordered (see Sections 9.12 through 9.14). The
temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or
Net.
Field
Setup
Menu
Operating Range
Temp. Units
Temp. Input
Zero Calibration
Temp. Range
(Fixed/Variable/Net)
Eng. Units
Temp Input
Lockdown
Fixed
Value
(Variable)
Flow
Correction
AutoZero
Temp. Comp.
Meas. Fl. Disp. Fltr