MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
23
Revision Level 002
8.4.2. Lockdown
Delay
The Lockdown Delay Menu allows the user to enter a lockdown time delay (0-20 seconds) that will
delay the display and output lockdown from occurring until the flow value or output value has remained
below the lockdown value for that duration.
Field Setup
Menu
Operating Range
Lockdown
Zero Calibration
(0-20%)
Eng. Units
(10%)
Lockdown
Flow Correction
Delay
Auto Zero
(0-20 seconds)
Temp. Comp.
(2)sec
Meas. Fl. Disp. Fltr
8.5. FLOW
CORRECTION
The Flow Correction Menu was incorporated into the MicroTrans
II
to give the user an easy way to make
corrections to the display and output without changing the Op. Range Value entered by the factory or
user. The Flow Correction Menu would be used to correct for a constant error from zero to the entered
Op Range Value. The following menus are only available if the MicroTrans
II
is configured by Paragon
at the time of order for flow or velocity.
8.5.1. Flow Correction (K-Factor Calculator)
If the new K-factor Value needs to be calculated, select the K-Factor Calc. Menu, enter the MicroTrans
II
Total Displayed Value and Total Measured Value (value measured by a balancer), press Enter and the %
change will be calculated and stored as the new K-Factor Value.
Field Setup
Menu
Operating Range
Flow Correction
Calculated
Zero Calibration
Displayed Value:
Eng. Units
K-Factor Calc.
(000,000) CFM
Lockdown
Measured Value:
Flow Correction
K-Factor
(000,000)
CFM
Auto Zero
K-Factor Range
Temp. Comp.
(0.085/1.300)
Meas. Fl. Disp. Fltr
K=(01.000)