Summing Operation & Maintenance Manual
Paragon Controls Incorporated
25
Revision Level 002
8.6.2. AutoZero
Interval
The AutoZero Interval Menu allows the user to select the AutoZero Interval from once an hour to once a
day in 1 hour increments. Use the UP/DOWN buttons to select the interval value. Upon device power
up, an AutoZero cycle will occur after 20 seconds.
Field
Setup
Menu
Operating Range
Auto Zero
AZ Interval
Zero Calibration
AZ Status
(1 TO 24HR)
Eng. Units
AZ Interval
Lockdown
AZ Test Process
(01)HR
Flow Correction
Auto Zero
Temp.
Comp.
Meas. Fl. Disp. Fltr
8.6.3. AutoZero
Test
Process
For troubleshooting or testing the AutoZero function, the AutoZero Test Process Menu allows the user
to select an Auto Zero test frequency of once a minute to once every 30 minutes in 1 minute increments.
Use the UP/DOWN buttons to select the interval value. If AutoZero Test Process is turned ON for more
than 60 minutes, it will automatically default to OFF and the AutoZero Interval (see Section 8.6.2) will
be reactivated.
Field
Setup
Menu
Operating Range
Auto Zero
AZ Test Process
Zero Calibration
AZ Status
AZ Test
Eng. Units
AZ Interval
(ON/OFF)
Lockdown
AZ Test Process
(OFF)
Flow
Correction
Auto Zero
AZ Interval
Temp. Comp.
(1) Min
Meas. Fl. Disp. Fltr
8.7. TEMPERATURE
COMPENSATION
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection and Section 4.1 for
temperature input signal configuration.