Summing Operation & Maintenance Manual
Paragon Controls Incorporated
31
Revision Level 002
8.12. HIGH/LOW
ALARM
OPTIONS
The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm
option is purchased.
8.12.1. Alarm Status
The Alarm Status allows the user to independently turn each alarm ON or OFF.
Field
Setup
Menu
Output Filter
Alarm
Alarm Status
Alarm
Alarm Status
DP Display Format
Alarm Values
Low
Alarm:
Factory Defaults
Alarm Delays
(On)
High
Alarm:
(On)
8.12.2. Alarm Values
The Alarm Value Menu allows the user to enter the Low or the High flow or pressure alarm value.
Alarm values will be displayed in the same engineering units selected in the Eng. Units Menu (see
Section 8.3).
-
High Alarm Function:
The High Alarm activates if the flow or pressure exceeds the High
Alarm value and resets when the flow or pressure drops below the High Alarm Value.
-
Low Alarm Function:
The Low Alarm activates if the flow or pressure drops below the Low
Alarm Value and resets when the flow or pressure exceeds the Low Alarm Value.
Field
Setup
Menu
Output Filter
Alarm
Alarm Value
Alarm
Alarm Status
DP Display Format
Alarm Values
Lo
Alarm
Value:
Factory Defaults
Alarm Delays
(000,000)
Hi Alarm Value:
(100,000)