MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
35
Revision Level 002
9.1.3. Action
The Action Menu allows the user to select between Direct and Reverse Action. The controller Action
for various applications is listed in the below table.
Process Controlled
Control Variable
Action
Flow
Fan Variable Speed Drive
Reverse
Flow
Normally Closed Damper
Reverse
Flow
Normally Open Damper
Direct
Negative Duct Pressure
Fan Variable Speed Drive
Direct
Negative Duct Pressure
Normally Closed Damper
Direct
Negative Duct Pressure
Normally Open Damper
Reverse
Positive Duct Pressure
Fan Variable Speed Drive
Reverse
Positive Duct Pressure
Normally Closed Damper
Reverse
Positive Duct Pressure
Normally Open Damper
Direct
Tech.
Config.
Password:
1000
Controller Parameters
Controller Display
Action
Area Factor
Tuning Parameter
Direct/Reverse
Transducer Cal.
Action
Ext. Flow Source
Cont. Setpoint
(Reverse)
Ext. Flow Span
Output Start
Altitude
Alarm
ON/OFF
Process Output Menu
Output Override
Temp.
Output
Menu
9.1.4. Controller
Setpoint (Internal Value)
The Controller Setpoint Menu allows the user to enter an Internal Setpoint Value. The acceptable
setpoint range is 0 to the Operating Range Value entered.
Tech.
Config.
Password:
1000
Controller Parameters
Controller Display
Cont. Setpoint
Area Factor
Tuning Parameter
Transducer
Cal. Action (ACFM)
Ext. Flow Source
Cont. Setpoint
Ext. Flow Span
Output Start
(000,000)
Altitude
Alarm
ON/OFF
Process Output Menu
Output Override
Temp. Output Menu