If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Op Range will be
Reset to the MAX
F.S. Value
(Press Enter)
Area Factor
(FT )
(001.000)
Area Factor
(FT )
Accepted
(001.200)
Op Range Outside
Allowable Value.
Op Range Will be
Reset to MAX
F.S. Value
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Area
Factor and pressing
the Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
Enter Value
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Area Factor Example-