Summing Operation & Maintenance Manual
Paragon Controls Incorporated
46
Revision Level 002
9.8.4. Span
Calibration
The Span Calibration Menu allows the user to make output span adjustments. Span adjustments require
a low pressure air source adjusted to the Full Scale Value shown on the side label. Monitor the output
and with each Up or Down button depression, the output will increase or decrease by 0.01VDC or
0.01mA depending on output selection.
Tech Config
Password: 1000
Controller Parameters
Output Selection
Use Up/Down
Area Factor
Volt Out 5/10vdc
Buttons
Transducer Cal.
Min Calibration
To Adjust Output
Ext. Flow Source
Span Calibration
(Press Enter)
Ext. Flow Span
Return to Menu
Altitude
Process Output Menu
Temp. Output Menu
9.9. TEMPERATURE
OUTPUT
MENU
9.9.1. Voltage Output Level Selection
The Voltage Output Level Selection Menu allows the user to select either 0-5VDC or 0-10VDC for the
Temperature Output voltage signal. See Section 4.5 for switch selection.
Tech Config
Password: 1000
Controller Parameters
Volt Out 5/10vdc
Volt Out 5/10vdc
Area Factor
Min Calibration
Transducer Cal.
Span Calibration
(0-5V / 0-10V)
Ext. Flow Source
Return to Menu
Ext. Flow Span
(05) Volt
Altitude
Process Output Menu
Temp. Output Menu