Summing Operation & Maintenance Manual
Paragon Controls Incorporated
49
Revision Level 002
9.10.3. Span Calibration
The Span Calibration Menu allows the user to make output span adjustments. Span adjustments require
a low pressure air source adjusted to the Full Scale Value shown on the side label. Monitor the output
and with each Up or Down button depression, the output will increase or decrease by 0.01VDC or
0.01mA depending on output selection.
Tech Config
Password: 1000
Cont. Output Menu
Volt Out 5/10vdc
Use Up/Down
Correction Coeff.
Min Calibration
Buttons
4PT Flow Corr
Span
Calibration
To Adjust Output
MAC Address
Return to Menu
(Press Enter)
Instance Number
Modbus ID
Baud Rate
9.11. CORRECTION
COEFFICIENT
The Correction Coefficient Menu is only available if the MicroTrans
II
is configured by Paragon at the
time of order for flow or velocity. If the MicroTrans
II
is configured for input from a non-amplified
Pitot-type flow sensor (such as those manufactured by Paragon) the menu in Section 9.8.1 will be
displayed. If the MicroTrans
II
is configured for input from a piezometer ring or amplified differential
pressure flow sensor (manufactured by others) the menu in Section 9.8.2 will be displayed.
9.11.1. Probe Coefficient
The Probe Coefficient Menu allows the user to modify the formula constant of 1096.70 for a non-
amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000
Cont. Output Menu
Correction Coeff.
Correction Coeff.
4PT Flow Corr
Probe
MAC Address
(1,096.70)
Instance Number
Modbus ID
(001,096.70)
Baud Rate