MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
51
Revision Level 002
9.12. FOUR POINT FLOW CORRECTION
The Four Point Flow Correction Menu allows the user to make corrections to the display and output
signal at 20% increments between 20% and 80% of Operating Range Value entered. The Displayed
Value is a fixed value determined by the percentage of Operating Range. The Measured Value is the
value determined by an independent balancer’s reading. The Four Point Flow Correction Menu is only
available if the MicroTrans
II
is configured by Paragon at the time of order for flow or velocity.
Tech.
Config.
Password:
1000
Cont. Output Menu
80,000 ACFM
Display Value
Correction Coeff.
60,000 ACFM
(80,000)
4PT Flow Corr
40,000
ACFM
MAC Address
20,000 ACFM
Measured Value
Instance Number
(080,000)
Modbus ID
Baud Rate
80,000 ACFM
Display Value
60,000 ACFM
(60,000)
40,000
ACFM
20,000
ACFM
Measured Value
(060,000)
80,000
ACFM
Display Value
60,000
ACFM
(40,000)
40,000 ACFM
20,000
ACFM
Measured Value
(040,000)
80,000
ACFM
Display Value
60,000
ACFM
(20,000)
40,000
ACFM
20,000 ACFM
Measured Value
(020,000)