MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
58
Revision Level 002
TROUBLESHOOTING TABLE
SYMPTOM
SOLUTION
11. “AZ Error” text on display
1. Turn Power Switch Off and On to reset the
AutoZero valve
2. Check for a pinched tube beneath the main board.
(Caution: Remove power before removing board)
3. Contact
Factory
11. Controller Output stays at minimum
value.
1. Verify System Start contacts are closed (see
Section 3.1/J3 pins 13 and 14)
2. Verify Control Action is correct (see Section 9.1.3)
3. Verify Controller Setpoint Value is correct (see
Section 9.1.4)
4. Contact
Factory