VC-M-1 

Installation, Operation & Maintenance Manual 

OPTIONS 

EXTERNAL ALARM OPTION: 

This option feature allows the user to connect an audible or visual alarm apparatus located externally from 

the Mainframe. 

NOTE: To function, the Optional External Alarm Feature must also be present in the Mainframe., 

The alarm will activate if any of the properly optioned VC-M-1 modules in the mainframe go to an error 

condition (regardless of the audible ALARM feature setting in the Options Menu). 

Error Conditions: 

Open Heater/Triac (tOh)

Shorted Heater/Triac (tSh)

Over current Condition (HiC)

Open Thermocouple (tCO)

Shorted Thermocouple (tCS)

Reversed Thermocouple (tCr)

Ground Fault (gFd)

Internal Configuration Error (CAL, cFg, CFg)

Over or Under temperature condition (+/-30 º from setpoint)

High/Low Temperature Alarm Notes: 

First power up: When the module is first powered up, the Process Temperature will be below the

setpoint and have a low temperature condition, however, the module will not 

close the alarm contacts, since this is considered to be normal operation.  Once 

the Process Temperature enters the normal range of +/- 30

o

 (16° C) from setpoint, 

the alarm contact closure procedure will be enabled for any future high or low 

temperature conditions. 

Standby mode:  Placing the module into Standby Mode creates a temporary target temperature of

212

o

F. (100° C) If the Process Temperature at that time is +/- 30

o

 from 212

o

 F 

(100° C), the alarm contacts will close. 

Boost Mode:  Placing the VC-M-1 into Boost Mode creates a temporary target temperature

greater than the current setpoint (the temperature and time are set in the Options 

Menu). If the Process temperature at that time is +/- 30

o

  from the temporary 

Boost target temperature, the alarm contacts will close activating the external 

alarm. 

Operator Intervention: If an operator changes the setpoint, causing it to be +/- 30

o

  from the

Process Temperature, the alarm contacts will close activating the external alarm. 

Manual Mode:  The alarm contacts will not close for High/Low Temperature conditions if the

module is in Manual Mode. 

Phone: 800-521-0546   E-mail: sales@pcs-company.com   Fax: 800-505-3299

www.pcs-company.com

10

Summary of Contents for VC-M-1

Page 1: ...URES PAGE 6 MENU PARAMETER CHART PAGE 6 MENU PARAMETER SETTINGS PAGE 8 TROUBLE SHOOTING PAGE 9 OTHER FALSE ALARMS PAGE 10 OPTIONS EXTERNAL ALARM PAGE 11 PRODUCT SPECIFICATIONS PAGE 12 ADDENDUM Please...

Page 2: ...ipment or various parts WARNING When inserting or removing control modules from the main frame power must be turned off on both the module and main frame If the module is inserted or removed while und...

Page 3: ...PERATING FEATURES NORMAL OPERATIONS Auto Keys When the power switch on the module is turned ON the control module will look at the existing zone temperature and determine if the SOFT START cycle is ne...

Page 4: ...al alarm function ERROR CODES ALARMS INDICATORS ERROR CODES Displayed in process temperature upper window Error Code Description tCO An open thermocouple condition There is a break within the thermoco...

Page 5: ...IGH CURRENT WARNING To help protect valuable molds and other related equipment a safety device will alarm if a heater is drawing current above its rated capacity To set a current value scroll through...

Page 6: ...0 Amps 16 0 btp Boost Temperature Setting 0 100 30 bdu Boost Temperature Duration Setting 0 30 minutes 5 J K Thermocouple Type J or K SSL Soft Start Lock ON or OFF FPL Front Panel Lockout ON or OFF ME...

Page 7: ...t is activated Factory set at 30 F 16 C Boost has a selectable temperature range of 0 to 100 F 30 C bdu BOOST TEMPERATURE DURATION SETTING This parameter allows user to set the duration time the tempe...

Page 8: ...le for repairs Temperature won t settle on set point 1 Give module more time to settle on set point 2 Molding process may have a wide variation in temperature Check to see if changes in display temper...

Page 9: ...in the control module It indicates that there is more interference in the power line to the control system than the filtering in the power supply can accommodate A random occurrence is not cause for...

Page 10: ...close the alarm contacts since this is considered to be normal operation Once the Process Temperature enters the normal range of 30o 16 C from setpoint the alarm contact closure procedure will be ena...

Page 11: ...d transient pulse suppression Shorted Triac Heater Protection Highly sensitive fast acting relays cut power to load Power Line Isolation Optically and transformer isolated from AC lines Isolation volt...

Page 12: ...ent draw on the load heater and has the ability to detect a shorted or open load heater When set to rLy the module is not capable of measuring or displaying the current draw of the load heater and CAN...

Page 13: ...Phone 800 521 0546 E mail sales pcs company com Fax 800 505 3299 www pcs company com Turn To The Industry Experts...

Reviews: