ERRORS & ALARMS INDICATOR DESCRIPTION: 

OPEN THERMOCOUPLE PROTECTION: 

In the event a thermocouple fails in the open condition after reaching set point temperature, the module will 

automatically control temperature with stored APO (Average Power Output) information if the 

MENU 

feature 

“tCO” 

is set to 

“APO”, 

otherwise power is disabled. This feature only operates at set point temperature. 

REVERSED THERMOCOUPLE PROTECTION 

The VC-M-1 will scrutinize actual voltage through the thermocouple. In the  event  a  negative  voltage  is detected, 

the 

“tCr” 

error code will be displayed, and power will not be applied to the heater. 

SHORTED THERMOCOUPLE INDICATION: 

In the event a thermocouple fails to detect a rise in temperature while power is being applied to the heater, the module 

will activate an alarm, and the “

tCS” 

error code will be displayed.   The module activates 

“APO” 

if  selected, 

otherwise 

“OFF”. 

OPEN TRIAC/OPEN HEATER: 

The module will alert the operator in the event of an open triac or heater, by displaying a 

“toH” 

error message in the 

upper window. This condition is detected  if the heater fails  to  maintain or rise to set point temperature and there is 

an absence of current flowing to the heater. Module will disable power to heater. 

SHORTED TRIAC PROTECTION: 

Within the circuitry of the 

μATC

-20 module are relays which disable power to  the heater in the event  the main triac 

is shorted. In a situation when power to the  heater  is detected when the temperature  is well above the set point,  the 

module will disable power to the heater.   A 

“tSH” 

error code will then be displayed in the upper window so damage 

to the mold or heater can be averted. 

HIGH CURRENT WARNING: 

To help protect valuable molds and other related equipment, a safety device will alarm if a heater is drawing current 

above its rated capacity.  To set a current value, scroll through the 

MENU 

for the 

“HiC” 

feature, using the “up” 

or “down” keys set a value just above the heaters maximum current draw. The module will trigger an alarm and 

disable power to the heater if current exceeds the set value. Utilizing this feature can save time and expense by 

calling  attention to  a problem before  damage occurs.  In 

MENU 

the range may be set between 1.0 and 16.0 amps. 

GROUND FAULT SENSITIVITY: 

The control module is equipped with a ground fault detection circuit. When the 

“SOFT START” 

cycle terminates, 

the control module will check for current leakage to ground in the heater  circuit.   If leakage is detected in excess 

of the value entered in 

“gFS” MENU 

parameter, the control module  will  alarm and 

“gFd” 

will be displayed in 

the process temperature window. The ground fault sensitivity is factory set at 120mA. Sensitivity may be  adjusted 

or turned off in 

MENU 

option 

“gFS”

.  To disable  ground  fault, first set the option to 

“OFF” 

then turn the module 

off and then back on. (range 60 to 180 mA) Power will be disabled to heater. 

HIGH AND LOW TEMPERATURE ALARM: 

The high and low temperature alarms have been factory set at  +/- 30º  F (16° C).   If the zone temperature drops 30º 

(16° C) below the set point or if the temperature exceeds 30º  (16° C) above the set point, the alarm will activate, 

and the 

“HIGH” 

or 

“LOW” 

LED will activate. 

BLOWN FUSE INDICATION: 

In the event that one or both of the module power fuses blow, the red LED’s labeled 

“F1” 

or 

“F2” 

will come on indicating 

which fuse has blown. 

CAUTION

: only the proper fuses  must be  used  in order  to  prevent  module damage and void 

the warranty. Fuses are available from PCS. 

Phone: 800-521-0546   E-mail: sales@pcs-company.com   Fax: 800-505-3299

www.pcs-company.com

5

Summary of Contents for VC-M-1

Page 1: ...URES PAGE 6 MENU PARAMETER CHART PAGE 6 MENU PARAMETER SETTINGS PAGE 8 TROUBLE SHOOTING PAGE 9 OTHER FALSE ALARMS PAGE 10 OPTIONS EXTERNAL ALARM PAGE 11 PRODUCT SPECIFICATIONS PAGE 12 ADDENDUM Please...

Page 2: ...ipment or various parts WARNING When inserting or removing control modules from the main frame power must be turned off on both the module and main frame If the module is inserted or removed while und...

Page 3: ...PERATING FEATURES NORMAL OPERATIONS Auto Keys When the power switch on the module is turned ON the control module will look at the existing zone temperature and determine if the SOFT START cycle is ne...

Page 4: ...al alarm function ERROR CODES ALARMS INDICATORS ERROR CODES Displayed in process temperature upper window Error Code Description tCO An open thermocouple condition There is a break within the thermoco...

Page 5: ...IGH CURRENT WARNING To help protect valuable molds and other related equipment a safety device will alarm if a heater is drawing current above its rated capacity To set a current value scroll through...

Page 6: ...0 Amps 16 0 btp Boost Temperature Setting 0 100 30 bdu Boost Temperature Duration Setting 0 30 minutes 5 J K Thermocouple Type J or K SSL Soft Start Lock ON or OFF FPL Front Panel Lockout ON or OFF ME...

Page 7: ...t is activated Factory set at 30 F 16 C Boost has a selectable temperature range of 0 to 100 F 30 C bdu BOOST TEMPERATURE DURATION SETTING This parameter allows user to set the duration time the tempe...

Page 8: ...le for repairs Temperature won t settle on set point 1 Give module more time to settle on set point 2 Molding process may have a wide variation in temperature Check to see if changes in display temper...

Page 9: ...in the control module It indicates that there is more interference in the power line to the control system than the filtering in the power supply can accommodate A random occurrence is not cause for...

Page 10: ...close the alarm contacts since this is considered to be normal operation Once the Process Temperature enters the normal range of 30o 16 C from setpoint the alarm contact closure procedure will be ena...

Page 11: ...d transient pulse suppression Shorted Triac Heater Protection Highly sensitive fast acting relays cut power to load Power Line Isolation Optically and transformer isolated from AC lines Isolation volt...

Page 12: ...ent draw on the load heater and has the ability to detect a shorted or open load heater When set to rLy the module is not capable of measuring or displaying the current draw of the load heater and CAN...

Page 13: ...Phone 800 521 0546 E mail sales pcs company com Fax 800 505 3299 www pcs company com Turn To The Industry Experts...

Reviews: