Wiring Installation—STATE-SIDE GUIDELINES
Wiring guidelines - State-Side (U.S. Installations)
27
Typical Installation Breaker Box
Class A 50 amp, 120/240 volt, GFCI
TO BE NOTED:
Installation of this GFCI Circuit Break-
er, including ampere sizing and choice of qualified elec-
trician in accordance with the National Electrical Code,
and all applicable federal, state and local codes and regu-
lations in effect at the time of installation.
TO BE NOTED:
The white neutral wire from the back
of the GFCI Circuit Breaker MUST be connected to an
incoming Line Neutral. The internal mechanism of the
GFCI requires this Neutral connection for proper GFCI
function.
Ground to Spa
Ground Input
Load 120V
(Black) To Spa
Load 120V
(Red) To Spa
Load Neutral
(White) To Spa
To Spa (OUTPUT)
Line (BLACK)
House Input
Line (RED)
House Input
Pig Tail (WHITE) From GFCI
Breaker Going to Neutral
Bar in Box
Load Neutral Bar
Line Neutral (WHITE)
House Input
From House (INPUT)
IMPORTANT: 6 Gauge Copper Wire MUST Be Used
Test GFCI Monthly and Prior to Each Use.
ATTENTION ELECTRICIAN:
All PDC Spa Units must be installed with an approved G.F.C.I. in accordance with all
applicable codes. Installation of G.F.C.I. varies among those manufacturers. Follow
each manufacturer’s Guidelines to ensure proper operation and
protection of spa occupants. This diagram is a “Typical” installation to
be used only as a reference for the installing electrician.
PDC Spas does not supply the gfci.
Ground Bar Attached
To Box Input & Output
IF INSTALLING WIRING IN A CONDUIT ABOVE OR BELOW GRADE, FOR PROPER GFCI OPERATION
THE OPEN END (S) OF THE CONDUIT MUST BE HIGHER THAN THE SURROUNDING SURFACE TO
PREVENT WATER INTRUSION INTO THE CONDUIT.