Device Chain: Settings ___________________________________________________________
Ctrl Nr: PM375103 Revision: 003
25
4.2.4
BCMS CB Subfeeds Settings
In addition to its panelboard distribution, an RPP can have a two-subfeed distribution with its own
points list. (These are not the same as the Enhanced Subfeeds (ESF) points list which is for a
subfeed-type PDU.)
You can set only the device
NAME
and the software
VERSION
in
BCMS CB SETTINGS
(Figure 20).
Select (touch)
BCMS KWH
device name in
DEVICES
list. Device name turns blue when
selected.
NAME
: Enter a unique device name (up to 16
characters); device name is propagated to header
and device list.
START
: Number for first panelboard circuit, touch
to inc42 to next panelboard. Up to eight
(8) PBs are allowed:
1
(1-42),
43
(43-
84)…
295
(295-336).
NUMBERING
: Toggle panelboard numbering
layout
•
STANDARD
= Numbers increment in
numerical order (1, 2, 3… 42) down left side
first (1-21), then right side (22-42).
•
ODD/EVEN
= List circuits as they are laid out
on panelboard, odd numbered circuits on left
side, even numbered circuits on right side
(such as 1, 3, 5, …, 41 on left side, and 2, 4, 6,
…, 42 on right side).
Touch to set
VERSION
number for BCMS software (requires Version Number
Update Password). The new VERSION number appears in the SOFTWARE
VERSIONS list.
Touch
BCMS CB device name
in
DEVICES
list. Device name
turns blue when selected.
Available Settings
Touch
NAME
box to bring up keyboard where you
can enter the
Device NAME
(up to 16 characters).
The device name is propagated to the header and
device list.
Device name should be unique, so that alarms can
be associated with a specific device.
Set version: Touch
VERSION
box to enter
software versions. Keyboard appears requesting
password and then requests that you enter the
version code (enter “VNUP”).
Figure 20 Settings: BCMS Subfeeds
Figure 19 Settings: BCMS Device