BCMS (Normal) Panelboard Readings
Select
BCMS device name
in list (
BCMS
in this list). Device
name turns blue when selected and device name displays in
header.
Touch
READINGS
to see BCMS power monitoring data.
Panelboard totals
, using main feeds or
BCMS computed measurements:
PB Amps
: Total panelboard
measurements, phases ABCNG
% Load
: Percent of maximum PB load as
specified by user in points list
Both PBs
: Sum of phase ABCN
measurements for both panelboards (not
available if PBs operate at different
voltages)
Frequency
: Measurement in Hz
Panelboard instantaneous readings:
Voltage
AB, BC, etc., to panelboard with
THD (Total Harmonic Distortion %) by
phase:
Line 1 = voltage source 1
Line 2 = voltage source 2, if present
Panelboard power
measurements by
phases ABC and total:
KW
KVA
KVAR
PF
Panelboard cumulative reading:
KWH
panelboard total
Clear
= Reset KWH to 0.
Measurements and Alarms, individual
panelboard circuits
(42 circuits):
NO
= Circuit Number
AMPS
= Amperes
CB
= Circuit breaker rating (Amps)
MIN
= Lowest current read
MAX
= Highest current read
ZERO
: OK = Current has not dropped to 0
since last reset; ACTIVE = Current has
read 0 after having read a minimum current
WARNING
: OK = No warning outstanding;
ACTIVE = warning outstanding
ALARM
: OK = No alarm outstanding;
ACTIVE = Alarm is outstanding
Figure 25 Readings: BCMS (Normal)