WaveStar Static Transfer Switch 2000A 3-Pole
42
Ctrl Nr: PM375118-004
3. In
REDUNDANT
mode, the ROI can also be used to directly initiate a transfer using the
SOURCE
SELECTOR
momentary toggle switch.
NOTE1:
The
SOURCE SELECTOR
switch operates slightly differently in Normal and Redundant modes:
•
In Normal mode, it sets the Preferred Source control to Source 1 or 2, as selected. This can
cause a transfer, if other circumstances allow it.
•
In Redundant mode, it causes an immediate transfer to the specified source, if the target power
source is within specification and the load is not already on that source.
NOTE2:
The
MAINTENANCE
light on the ROI panel refers to the Maintenance Bypass, an internal switch
used by service personnel to disable MCCB/MCSW trip units during maintenance.