System Setup: Operation
Ctrl Nr: PM375118-004
57
9
System Setup: Operation
9.1
Configuration Screen
The
Configuration
screen (Figure 22) is setup by PDI at the factory and requires PDI authorization to make
changes, but any user can view the screen. Touch the
Config
button to view.
PDI uses the
Configuration
screen to describe the system to the Monitor software, which is common for all PDI
STS products. Parameters include physical characteristics (standalone or redundant system, contractor board
installation, fans, number of isolation MCSWs), power (voltages, frequency, KVA, etc.), and distribution options.
9.2
Switch Settings Screen
Touch the
Switch
button in the navigation buttons to display the
Switch Settings
screen (Figure 23). The
Switch
Settings
screen is used to select or adjust parameters for sense and transfer algorithms.
Two of the three main transfer parameters
—transfer algorithm and retransfer setting—are set on the
Switch
Settings
screen and require administrator or other higher level authorization. The remaining choice
—
Preferred
Source
—is set on the
Home
screen and requires operator-level authorization.
Figure 22 Configuration Screen