Chapter 6 Description of Function Codes
Group F05: Fault and Protection
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.00
Input phase loss protection
0: disabled
1: enabled
1
※
It is used to determine whether to perform input phase loss or contactor energizing protection.
≥
18.5KW G type drive provide the function of input phase loss protection.
<
18.5KW P type drive do not provide the function of input phase loss protection no matter
whether F05.00 is set to 0 or 1.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.01
Output phase loss
protectio
0: disabled
1: enabled
1
※
It is used to determine whether to perform output phase loss protection.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.02
Action selection at
instantaneous power failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
※
F05.03
Voltage rally judging time a
instantaneous power failure
0.00s
~
100.00s
0.50s
※
F05.04
Action judging voltage at
instantaneous power failure
60.0%
~
100.0%(standard
bus voltage)
80.0%
※
Upon instantaneous power failure or sudden voltage dip, the DC bus voltage of the AC drive
reduces. This function enables the AC drive to compensate the DC bus voltage reduction
with the load feedback energy by reducing the output frequency so as to keep the AC drive
running continuously.
If F05.02 = 1, upon instantaneous power failure or sudden voltage dip, the AC drive decele
-
rates. Once the bus voltage resumes to normal, the AC drive accelerates to the set frequen
-
cy. If the bus voltage remains normal for the time exceeding the value set in F05.03, it is
considered that the bus voltage resumes to normal.
If F05.02 = 2, upon instantaneous power failure or sudden voltage dip, the AC drive deceler
-
ates to stop.