Value
Function
Description
38
PID integral pause
After this terminal becomes ON, the integral adjust-
ment function pauses. However, the proportional and
differentiation adjustment functions are still valid.
39
Reserved
reserved
40
Reserved
reserved
41
Motor selection
terminal 1
Switchover among the two groups of motor parame-
ters can be implemented through the two state
combinations of these 2 two terminals.
42
Reserved
reserved
43
PID parameter
switchover
If the PID parameters switchover performed by me-
ans of DI terminal (F10.18 = 1), the PID parameters
are F10.05 to F10.07 when the terminal becomes
OFF; the PID parameters are F10.15 to F10.17 when
this terminal becomes ON.
44
Reserved
reserved
45
Reserved
reserved
46
Speed control/Torque
control switchover
This terminal enables the AC drive to switch over
between speed control and torque control. When this
terminal becomes OFF, the AC drive runs in the
mode set in A03.23. When this terminal becomes
ON, the AC drive switches over to the other control
mode.
47
Emergency stop
When this terminal becomes ON, the AC drive stops
within the shortest time. During the stop process, the
current remains at the set current upper limit. This
function is used to satisfy the requirement of
stopping the AC drive in emergency state.
48
External STOP terminal
2
In any control mode (operation panel, terminal or
communication), it can be used to make the AC drive
decelerate to stop. In this case, the deceleration time
is deceleration time 4.
49
Deceleration DC
braking
When this terminal becomes ON, the AC drive
decelerates to the initial frequency of stop DC
braking and then switches over to DC braking state.
Chapter 6 Description of Function Codes
-134-
C
h
a
p
te
r
6
Peaco Support FC280 Series VFD User Manual
www.peacosupport.com sales@peacosupport.com Free Shipping Worldwide Reliable Supplier
PEACO SUPPORT