Value
Function
Description
37
frequency lower limit
reached(having
output at stop)
If the running frequency reaches the lower limit, the
terminal becomes ON. In the stop state, the signal is
still ON.
38
alarm output(keep
running)
If a fault occurs on the AC drive and the AC drive
continues to run, the terminal outputs the alarm signal.
39
motor overheat
warning
If the motor temperature reaches the temperature set
in F05.59 (motor overheat warning threshold), the
terminal becomes ON.
40
current running time
reached
If the current running time of AC drive exceeds the
value of F09.54, the terminal becomes ON.
Chapter 6 Description of Function Codes
-149-
Function
code
Name
Description
(setting range)
Factory
Default
Change
F07.06
Output terminal valid
mode selection
0: Positive logic
1: Negative logic
Unit's digit: HDO
Ten's digit:TA
Hundred's digit: RA
Thousand's digit: MO1
0000
※
It is used to set the logic of output terminals HDO, relay 1, relay 2, Mo1.
0: Positive logic
The output terminal is valid when being connected with COM, and invalid when being discon-
nected from COM.
1: Positive logic
The output terminal is invalid when being connected with COM, and valid when being discon-
nected from COM.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F07.07
HDO delay time
0.0s
~
3600.0s
0.0s
※
F07.08
TA delay time
0.0s
~
3600.0s
0.0s
※
F07.09
RA delay time
0.0s
~
3600.0s
0.0s
※
F07.10
Mo1 output delay time
0.0s
~
3600.0s
0.0s
※
C
h
a
p
te
r
6