Display
Fault name
Possible Causes
Solutions
E00F
EEPROM
readwrite
fault
u
The EEPROM chip is
damaged.
u
Replace the main control
board.
E012
Power input
phase loss
u
the three-phase power
input is abnormal.
u
the drive board is faulty.
u
the lightening board is
faulty.
u
the main control board is
faulty
u
eliminate external faults.
u
seek technical support
u
seek technical support
u
seek technical support
E013
Power output
phase loss
u
the cable connecting the
AC drive and the motor
is faulty.
u
the AC drive's three-
phase outputs are
unbalanced when the
motor is running.
u
the drive board is faulty.
u
the module is faulty.
u
eliminate external faults.
u
check whether the motor
three-phase winding is
normal.
u
seek technical support
u
seek technical support
E015
Current
detection fault
u
the HALL device is
faulty.
u
the drive board is faulty.
u
replace the faulty HALL
device.
u
replace the faulty drive
board.
E016
Motor self-
learning fault
u
the motor parameters
are not set according to
the name-plate.
u
the motor self-learning
times out.
u
set the motor parameters
according to the nameplate
properly.
u
check the cable connecting
the AC drive and the motor.
E017
Contactor
fault
u
the drive board and
power supply are faulty.
u
the contactor is faulty.
u
replace the faulty drive
board or power supply
board.
u
replace the faulty contactor.
Chapter 7 Fault Diagnosis and Trouble Shooting
-195-
C
h
a
p
te
r
7
Peaco Support FC280 Series VFD User Manual